beautypg.com

Aerovent IM-500 User Manual

Page 11

background image

11

Aerovent IM-500

flame MUST be a “clean blue flame”. A little yellow

tipping is acceptable, but the flame should be blue. The

flame length should be a maximum of 10-12 in.

3. Reconnect the wires to terminals #4.

Low Fire or By-Pass Adjustment

1. Disconnect wire from terminal #8 on the A1044 or

A1014 Amplifier. This causes valve to call for continu-

ous low fire.

2. Remove cap (B), Figure 12, and loosen lock screw (C).

Turn (D) to desired low fire adjustment. (Clockwise

rotation reduces minimum flow rate.) Flame should be

stable over full length of burner.

3. Tighten set screw (C), replace cap (B) and reconnect

wire to terminal #8.

NOTE: This procedure is in the Maxitrol bulletin found at

www.maxitrol.com. Please consult it for further information.

Blocking Main Gas and Vent Valve Systems for

FM and/or IRI Insurance Requirements

To meet the national insurance requirements of FM

(Factory Mutual) or IRI (Industrial Risk Insurers) these

controls are furnished in addition to the gas controls

required by ANSI.

Motorized Main Gas Valve(s)

FM and IRI (and some local codes) require the use of one

or two motorized main gas shut off valves and depends on

the BTU input capacity of the burner.

The motorized gas valve contains a heavy duty spring

which will return the valve to the closed position if power

is interrupted to the valve. The valve uses a hydraulic pump

to open the valve. The use of self closing heavy duty return

springs provides a positive shut off in the event of a power

loss to the valve. A second blocking valve prevents gas

escaping into any occupied space should the main gas valve

not provide tight shut-off when the unit is shut down.

High-Low Gas Pressure Switch (FM/IRI)

(Aerovent Part #470-01E)

A high and low gas pressure switch is included with all

units. These switches monitor the gas pressure downstream

from the safety valves and shuts off the electric supply to

the safety valves if excessive or insufficient gas pressure is

experienced. This will shut down all gas flow to the burner.

The switches must be manually reset when the gas pressure

is returned to the set point pressure of the respective pres-

sure switches.

Normally Open Vent Valve

CAUTION:

Units mounted indoors and supplied with a vent valve

MUST have the vent valve vented to the outdoors. Venting

of the valve is the responsibility of the installer.

Normally, two motorized main gas valves are supplied

and an open vent valve is also supplied between the two

valves. The vent valve

MUST BE VENTED TO THE

OUTDOORS.

The ASCO vent valve is a normally open solenoid type

valve. This valve is normally open when the unit is not

operating. It vents the pipe connecting the two safety shut-

off valves to the outdoors.

The vent valve should be checked for proper operation

at least once a year at the beginning of the heating season.

Obviously, if this valve should fail, large quantities of fuel

would be wasted, as this would be bypassed to the outside.

The purpose of the vent valve is to divert the gas flow

to the outdoors in the event the first motorized valve fails

to close during a shut down operating condition.

Figure 13. Valve Actuator and Gas Valve

Figure 14. High/Low Gas Pressure Switch