beautypg.com

Aerovent IM-500 User Manual

Page 14

background image

14

Aerovent IM-500

11. Turn unit off IMMEDIATELY and check the blower

for proper rotation of wheel. Correct if required by

reversing two of the three leads supplying power from

the starter. If soft start or VFD is installed consult the

instruction manual that was included with the unit to

change rotation.

12. Turn unit back on and check to make sure that the

damper opens fully without binding, also check the

motor and blower speed with the strobe for rpm.

13. With the voltmeter check motor voltage on all three phas-

es of the systems to make sure all legs are in balance.

14. With the amp meter check motor amp draw to make

sure it does not exceed the motor nameplate rating. On

three phase systems, check all legs to insure system is

balanced.

NOTE: The first main gas hand cock will have to be

opened at this time and the high and low gas pressure

switches must be reset. However, the second main hand

valve, (located before the modulating gas valve) should be

kept in the closed position.

15. Recheck gas supply pressure. Gage should show pres-

sure as marked at the gage.

16. Check pilot and pilot ignition. Open pilot gas hand

cock only.

17. Check to make sure that all manual reset safety devices

have been reset to their normal operating position.

18. Move the Summer/Off/Winter switch to “Winter”.

Move temperature controls to call for heat.

NOTE: The mild temperature control set point needs to

be set above the ambient outside temperature to allow the

pilot and igniter to function. (Do not forget to reset to 65

o

F

after final system checks are completed.)

19. Check to see that the pilot lights properly. The spark

igniter should begin to spark in approximately 10 sec-

onds and pilot flame should be established within 10

seconds.

20. The unit is supplied with an ultra violet flame detec-

tor (UV) scanner. With the UV detector (scanner), the

output of the detector should be stable and should be

between 1.25 and 5V DC at the flame relay terminals.

Adjust pilot regulator if the readings are outside of the

specified ranges by removing cap screw and adjusting

pilot flame with pilot needle valve. Best results are

obtained with smallest possible flame

1

/

2

- 1

1

/

2

turns

clockwise from fully closed position.

21. Check to make sure the flame sensor and flame safe-

guard relay is operating correctly. To check, shut off

the pilot gas hand valve while the pilot is still on. The

pilot igniter should try for ignition within 2 to 4 sec-

onds. If pilot cannot be reestablished, the flame safe-

guard control should go into lockout.

(If the flame

safeguard does not go into lockout, contact

factory.)

22. Turn the pilot gas hand cock to the on position and

reset the flame safeguard relay using the manual reset

button on the relay. Allow the unit to establish pilot.

23. Check the airflow sensing device switch by blocking

off 30% of the inlet to the unit. The system should

shut down. With the pilot established, increase the

pressure setting of the airflow proving switch by turn-

ing the adjustment screw on the switch clockwise.

Increase the setting until the pilot drops out. Back off

of this setting two turns enough to allow the pilot to

reignite.

(If pilot does not drop out during this

check, inspect the switch for damage and

replace if required.)

24. Check continuity of limit control contacts and wiring.

(Unit will not try for ignition if limit control

is faulty.) The high limit control is factory set and

does not require field adjustment.

NOTE: THE MAXIMUM GAS PRESSURE GAS

MANIFOLD CAN SAFELY HANDLE WITHOUT

DAMAGING THE CONTROLS IS 5 PSI.

25. Open main gas cock and check gauge gas pressure

reading. The pressure reading on the gauge should be

at factory noted hash mark.

(See unit rating or

system spec for high fire burner pressure

setting. Also see manifold component dia-

grams.)

26.

Observe low fire flame to make sure it LIGHTS

ACROSS THE ENTIRE LENGTH of the burn-

er is stable and burning with a clean blue flame.

27. Move the Maxitrol temperature setting control to its

highest setting and observe the high fire flame. Make

sure that it is stable and burning clean. A slightly

orange tip may be evident and is acceptable.

28. High Fire Adjustment: Disconnect lead #4 on series

14 or leads #2 and #4 on series 44 from the amplifier

which will cause the burner to go to a high fire condi-

tion. The flame length should be 10 in. and burn with

a slight orange tip. Adjust the pressure regulator in the

Maxitrol valve accordingly by removing the seal cap

adj. pressure reg. screw (should give manifold pressure

of 7 in.) Return wires to terminals when adjustments

are complete.

29. Low Fire Adjustment: Disconnect wire from term #8

in the amplifier. Remove cap and obtain a flame that is

a “ribbon” across the entire burner being sure flame is

stable. Tighten the setscrew, replace the cap and recon-

nect wire to term #8.

30. Check the burner gas pressure at high fire to make sure

the unit is not over or under fired.

If the burner is not firing at the pressure marked

on the unit’s gas pressure gauge, adjust the main

supply pressure regulator accordingly.

31. After the high fire pressure has been checked and reset

if necessary, turn the temperature controls down to

their lowest setting and recheck the low fire burner

flame. It should still be stable and burning clean.