beautypg.com

Aerovent IM-250 User Manual

Air cooler, Im-250

background image

Air Cooler

©1997 Aerovent

1. If air cooler is furnished with protective paint, the washer

surfaces should be inspected after installation is completed.

Any painted areas damaged due to welding, scratching, etc.,

should be retouched. Once a year the interior and exterior

should be examined and repainted if necessary.

2. Drain and thoroughly clean the tank, eliminators and baf-

fles as required to maintain clean water and surfaces. Dirty

operation not only reduces washer life and efficiency, but

also affects maintenance and operation of the total system.

Eliminators should be inspected with the following check-

list:

a. Periodically inspect side and top seals for leaks.
b. Check minimum water level.
c. Clean blades as required. Cleaning can be effected by

flushing the blades from both sides with a high pressure

water hose. Use a flexible round brush to clean out the

corrugations. Routine cleaning in this manner will usu-

ally prevent the necessity of using any cleansing agent.

d. Do not remove the blades for routine cleaning.
e. Once a year the blades may be removed for a thorough

cleaning.

f. Inspect top plate assembly while blades are out.
g. Do not force solid objects between the blades for any

purpose.

3. Two sets of suction screens are furnished with each wash-

er. One set should be in the washer tank at all times.

Screens should be inspected daily. If screens are dirty,

insert clean screens and remove dirty ones. Clean dirty

screens with hose.

4. Spray nozzles should be checked regularly for uniform

operation. Any nozzle partially clogged or worn should be

cleaned or replaced. An easy way to inspect nozzles is to

reduce spray pressure on the nozzles so that they can be

seen through the observation door.

5. After operating for a short period, examine the interior of

air washer for any scale deposit. Samples of make-up water

should be analyzed to determine if water treatment is

required. Where water treatment is not used, a continuous

flow of water is recommended through the overflow to

reduce concentration of solids, salts and acid in the tank.

6. If water carryover is observed, the following should be

noted and corrective action taken:

a. Carryover on eliminator blades is of two general types:

mist and droplet.

b. Mist is usually the result of high spray pressure and/or

bent or defective blades.

c. Droplet carryover is usually the result of low or high air

velocity, bent or defective blades, dirty blades, and/or

grease or other insoluble substances on the blades.

d. Carryover from leaks at the seals would be in droplet

form.

e. Low water level will cause carryover from under the

blades and excessive foaming.

f. Carryover of droplets can also be caused by improper

seating of the top plate assembly.

7. The complete manifold and riser assembly may be drained

by removal of the threaded PVC plug located on the under-

side of the manifold tee. Drain complete unit, including

pump, for winter storage.

General Installation, Operation and Maintenance Instructions For Aerovent Products

IM-250

June 1997

Aerovent | www.Aerovent.com

5959 trenton Lane n | minneapolis, mn 55442 | Phone: 763-551-7500 | Fax: 763-551-7501

®