Aerovent IM-500 User Manual
Page 10
10
Aerovent IM-500
Adjustable Pilot
(Aerovent Part #1192-01E)
The pilot is properly adjusted at the factory; however, the
conditions of the installation can affect this pre-adjusted
pilot so that it may require resetting. The pilot has a needle
valve adjustment under the brass screw cap. Remove the
brass screw cap to make the pilot flame adjustment. The
pilot works best with the smallest possible flame, and this
is usually with the needle valve screw backed out
1
/
2
to 1
1
/
2
turns from the fully closed position.
There are three (3) fully modulating temperature
control systems offered:
1.
OUTLET TEMPERATURE CONTROL SYSTEM
(OTC, Series 14) holds constant outlet temperature
adjustable at the remote operating station and has out-
door temperature compensation.
The discharge air temperature thermostat actuates
the modulating regulator to hold average outlet tempera-
ture to a set point located in the remote station.
2.
OUTLET TEMPERATURE CONTROL SYSTEM
(OTC-RO, Series 14 w/T115 Override) with room over-
ride (Optional) A T115 room space temperature control
increases the discharge air temperature until room tem-
perature is satisfied. The room set point is adjustable.
This system does not allow a room to fall below the
set point of the Room Override thermostat. Once the
room thermostat is satisfied, the temperature is then
backed down to the TD114 set point. The increase of
temperature is controlled set by a selector dial on the
back of the TD114.
Discharge air temperature thermostat automatically
limits extreme changes in discharge temperature.
3.
MODULATED ROOM TEMPERATURE CONTROL
(MRTC, Series 44) (Optional) maintains room tempera-
ture within very narrow limits, provides extreme accu-
racy and rapid response to small temperature changes.
Compensates for process heat while maintaining the
room temperature.
Go to the Maxitrol web site at www.maxitrol.com for
the Maxitrol bulletin that pertains to the system supplied
with your unit. The front specification page lists the type
of temperature control system.
Maxitrol Temperature Control Modulating Gas
Valves (MR212 valve)
Units are supplied with a Maxitrol Series 14 or 44 tempera-
ture control modulating system. The Maxitrol temperature
control responds to a DC voltage signal from the Maxitrol
Series 14 or 44 amplifier. When the DC voltage is in the
range of 0 to 5 volts the main valve is at low fire; modulates
between 5 and 15 VDC; at 15 volts the valve is full open
and is at high fire operation. As the DC voltage changes,
a solenoid valve in the main valve modulates. Low fire is
accomplished by means of a mechanical bypass built into
the valve body. This adjustment is located under the valve
cover and should be adjusted on all installation start-ups.
Maxitrol Modulating Valve Adjustment
NOTE: Low fire adjustment should be checked whenever
the high fire adjustment is changed.
High Fire Manifold Adjustments
1. Disconnect wires from terminals #2 and #4 on the
A1044 or #4 on A1014 Amplifier. This causes the valve
to call for continuous high fire.
2. Remove seal cap (A), Figure 12, and turn regulator pres-
sure adjusting screw to obtain desired manifold pressure.
(7 in. w.c. MAXIMUM) (Clockwise rotation increases
pressure.) The manifold pressure must not exceed 7
in. w.c. The flame must always be checked visually. The
Figure 10. Adjustable Orifice
Figure 11. MR212 Valve
Figure 12.