beautypg.com

Unit location restrictions and considerations, Sound and vibration levels, Installation – Aerovent IM-500 User Manual

Page 4

background image

4

Aerovent IM-500

B. All installation of this equipment must be performed

by a qualified installation agency only defined in ANSI

Z223.1.

C. Electrical ANSI/INFPA #70-1987.
D. Aircraft hangar NFPA 409.
E. National Fuel Gas Code NFPA 54.
F. Installation of air conditioning and ventilating systems

NFPA 90A.

G. Parking Structures and Repair Garages NFPA 54.1.

Unit Location Restrictions and

Considerations

CAUTION

Units must not be installed where they may be exposed

to explosive or flammable atmospheres. In Canada, only

100% make-up air direct-fired units may be installed and

they must be applied solely for replacing exhausted inside

air with heated outside air.

1. Do not locate any gas-fired equipment where chlori-

nated or acid vapors are present in the combustion air

atmosphere.

2. When locating units, consider general space and heat-

ing requirements and availability of gas and electrical

supply.

3. Maintain minimum clearances to combustibles. The

minimum clearances are, 12" from the top, 12" from

the bottom, 12" from the sides, and 12" from the

ends.

4. Where necessary to provide working clearance beneath

the unit, the unit shall be installed at a suitable height

above the floor or otherwise adequately protected.

5. Allow 36" clearance on both sides of the unit for ser-

vice access.

6. Do not modify or block combustion or ventilation

openings. Do not modify burner profile opening.

7. Do not install direct-fired units down stream from any

cooling system that utilizes refrigerants for cooling.

8. Be sure the structural support at the unit location is

adequate to support the weight of the unit.

9. Units require field support of the accessory filters and

inlet hood.

10. Some models may be split shipped to accommodate

maximum shipping widths. When assembling unit sec-

tions, make sure that the sections are properly caulked

and secured before operating the equipment.

11. Provide sufficient airflow across the burner. Refer to

unit data sheet for required airflow (cfm).

12. Units with motor horsepower below 7.5 hp are sup-

plied with an adjustable motor sheave. Units with 7.5

hp motors and above are supplied as standard with

fixed motor and blower drives. Units are supplied from

the factory with drives set for static pressure conditions

provided at the time of order. Check to make sure the

actual job site conditions match the conditions for

which the unit was ordered. If proper airflow cannot

be established with the drives furnished with the unit,

contact the factory for information on drive changes.

13. For economical installation and operation, locate each

unit close to the space it will serve, and close to the

utilities that will serve the unit.

Site Preparation

Before attempting to install the unit, be sure the site is

properly prepared.

1. Make sure there is enough clearance around the instal-

lation site to properly and safely rig and lift the equip-

ment.

2. Watch for overhead power lines, or nearby utilities to

prevent accidental contact and damage.

3. Make sure the unit supports are adequate to support

the equipment.

Sound and Vibration Levels

All mechanical equipment generates some sound and vibra-

tion that may require attenuation. Locate the equipment

away from critical areas whenever possible. Frequently units

can be mounted above utility areas, corridors, restrooms,

and other non-critical areas. Generally a unit should be

located within 15 feet of a primary support beam. Smaller

deflections mean less vibration and noise transmission.

Field installed, factory supplied vibration iso-

lators are available for suspended or rail/slab

mounted units. Internal, factory mounted blow-

er and motor isolation may be ordered as an

option at the time the unit is ordered.

Installation

Duct Connections

To assure proper airflow from the discharge of the unit

follow these recommendations:

1. Be sure properly sized and designed discharge ducts

are installed. Velocities should be selected from 2,000

ft/min to no more than 3,000 ft/min for optimum effi-

ciency of operation.

2. Units should have a common discharge plenum of at

least three (3) hydraulic duct diameters.

3. As a general rule, all discharge ducts should have a

straight run of at least three (3) hydraulic duct diameters

before making turns in the ductwork.

Hydraulic Duct Diameter for Rectangular Ducts

= Dh = 4A/P

Hydraulic Duct Diameter for Circular Ducts

= Dh = D

Where:

Dh = Hydraulic Diameter

A = Cross Sectional Area of Rect. Duct

P = Perimeter of Rectangular Duct

D = Diameter of Round Cut