36. Mild weather control cycled and reset to proper setting (65
o
F)
37. Air flow proving switch cycled for functionality by blocking off
1
/
3
of system inlet.
38. High temperature limit control cycled for test by lowering set point checked for functionality required
manual reset.
39. Low temperature limit & timer. Set low limit above the ambient temperature. Set timer to 1 minute. Unit
should shut down after timer times out. After shut down reset timer to 3 minutes. Reset unit and restart.
40. Does flame modulate in response to temperature set point changes?
41.
Recirculating Systems ONLY: Burner by-pass and return air damper operating correctly when setting
changes on rheostat or static pressure sensing device dampers should modulate to new position and
maintain stability.
42. Do all dampers return to closed position with power interruption? (On recirculation system return air open
outside air closed.)
USE BACK OF REPORT FOR COMMENTS
DATE OF INSTALLATION
Name, address and phone number of company doing installation:
Technician Signature:
Date:
Return the start-up report to your sales representative to activate the warranty. The represetative will then re-
turn the report to the factory. Please keep a copy for your records. Contact Aerovent at (937) 473-3788 if there
are any questions.
DATE OF START-UP
Name and address of company doing start-up:
Technician Signature:
Date:
Return the start-up report to your sales representative to activate the warranty. The represetative will then re-
turn the report to the factory. Please keep a copy for your records. Contact Aerovent at (937) 473-3788 if there
are any questions.