beautypg.com

Aerovent IM-500 User Manual

Page 12

background image

12

Aerovent IM-500

outside air. When power is interrupted to the motors, the

return air damper closes and the profile damper opens. The

discharge damper closes also giving a 100% shut-off from

outside air.

CAUTION:

The building pressure control’s low pressure tap MUST

be vented to the outdoors and fitted with a wind and rain

shield.

The desired building pressure is maintained by adjusting

the pressure set point on the floating pressure switch. The

differential is adjusted by the null adjustment in the pres-

sure switch. The smaller the null zone the more sensitive

the setting. The larger the null zone, the less sensitive the

setting. Settings should be such that the dampers stabilize

and hunting of the damper motors does not occur. The

larger the null zone the more stable the control loop will be.

Reset Timer

(Aerovent Part #21749-01)

Timed bypass of the low temperature switch. A timed

freeze protection system is supplied with most units. This

system includes a reset timer and a discharge air tempera-

ture sensor (freeze stat). On initial start-up, the reset timer

allows the unit to go through the normal ignition sequence.

The reset timer is set to engage the discharge air sensor

after a period of 3 minutes. In the event the unit fails to fire

after this time period the discharge air sensor will sense the

cold air and will shut down the entire unit. This is done to

prevent freeze up of water lines and minimize discomfort

to personnel in the area.

Figure 15. Vent Valve

Building Pressure Controls (Optional)

When units are provided with an 80/20 recirculating fea-

ture, a separate outside air and return air damper control is

supplied with the unit.

The control includes a floating pressure switch. Units

utilizing a building pressure control are provided with an

outside air burner bypass damper and a return air damper.

The outside air burner bypass damper and return air damp-

er are controlled by a floating damper motors. The dampers

are connected to the motor by a damper linkage.

The purpose of the building pressure switch is to sense

the difference between the indoor building pressure and

outdoor atmospheric pressure. This system is used when

varying exhaust loads are handled by one make-up air unit.

As more exhaust fans are turned on, pressure in the

building will tend to become more negative. The building

pressure switch senses this change in pressure and causes

the floating damper motor to adjust its position to bring

the building pressure back to near atmospheric by intro-

ducing more outside air and reducing the amount of return

air supplied to the unit. The dampers can be adjusted for

a maximum of 100% outside air, and a minimum of 20%

Figure 16. Floating Pressure Switch

Figure 17. Reset Timer