beautypg.com

Myron L Aquaswitch II User Manual

Page 39

background image

B .

“PURGE CYCLE” CALIBRATION

PROCEDURE

The Purge Cycle control adjustment (see figure V.A.1) determines
the time span that the Bleed and Process solenoid valves are
energized during either a Bank A or B Purge Cycle.
Turning the adjustment screw fully clockwise equals a minimum
Purge Cycle of approximately one (1) minute. Turning the
adjustment screw fully counterclockwise equals a maximum
Purge Cycle of nine (9) to thirteen (13) minutes.

1.

Being careful not to excessively strain the cable(s),
unfasten the enclosure’s front panel.

2.

Turn the Logic Board adjustment to the desired Purge
Cycle setting. See figures V.A.1 and V.B.1.

C .

“ALARM RESET” MODE CHANGE PROCEDURE

The

AQUASWITCH I

and

AQUASWITCH II

are shipped with

an Alarm condition that occurs whenever the “IN USE” Banks are
switched automatically.
This section provides the user with the procedures for activating
an Alarm condition every time the “BANK SWITCH” is manually
pressed.
NOTE: The Manual Bank Switch alarm condition is in addition to
the standard Automatic Bank Switch alarm condition.
To activate the Manual Bank Switch alarm condition, the user
must reinstall the Logic Module Alarm Reset jumper as shown in
figure V.C.1.

1.

Being careful not to excessively strain the cable(s),
unfasten the enclosure’s front panel.

2.

Remove the Logic Board Jumper and reinstall as shown
in figure V.C.1.

36

Figure V.B.1

AUTO/MANUAL

RESET

AUTO

RESET

"ALARM RESET" JUMPER DIAGRAM

For alarm jumper location, see figure V.A.1

AQUASWITCH

LOGIC BOARD

Figure V.C.1

1

13

AQUASWITCH

LOGIC BOARD

SET FULLY

CLOCKWISE

FOR ONE (1) MINUTE

PURGE CYCLE

SET FULLY

COUNTERCLOCKWISE

FOR 9-13 MINUTE

PURGE CYCLE

"PURGE CYCLE" ADJUSTMENT CONTROL

For alarm jumper location, see figure V.A.1

Figure V.A.2

AQUASWITCH II™

ELECTRICAL CONNECTION DIAGRAM

AQUASWITCH™

POWER BOARD

SENSOR

L N

0-10VDC
OUTPUT

NEU
GRN
RED
WHT
BLK

(+)
(-)

CONTROL
RELAY

MAIN AC
INPUT
POWER
FROM AS

NEU-WHT
LINE-BLK

MONITOR/CONTROLLER
MAIN CIRCUIT BOARD

}

{

}

FUSE

115/230
SWITCH

SOLENOID
VALVE
OUTPUT
POWER

BANK B
BANK A
BLEED
COM

MAIN
INPUT
POWER

GRN
ORN
WHT

NC

NO

COM

GRD

C

PWR

ALARM
RELAY

NO

COM

NC

FUSE
1/8 Amp
AGC 1/8

WHT

BLK

SOLENOID
INPUT
POWER

LINE
NEUTRAL

BK B

BK A

BLD

COM

LOGIC
BOARD
CONNECTION

FUSE*

115/230
SWITCH

TRANSFORMER

*115/230VAC
FUSE
100mA
(T.10A) 5X20
Slow Blow/
Time Delay
*24VAC
FUSE
250mA
(T.25A) 5X20
Slow Blow/
Time Delay

115/230
JUMPERS

OR

}

}

LINE / +DC
(BLK)
NEUTRAL / -DC
(WHT)

{

{

This manual is related to the following products: