1.

Using the “SET POINT CHECK” switch, verify that the
display indicates the desired Set Point.

NOTE: If the display does not indicate the correct Set Point
setting, reference Section IV.B.2 and figure V.A.1 for the
procedures to readjust the

AQUASWITCH II

’s internal Set

Point.

2. Observe reading of water being monitored.
3. With front panel removed, press “SET POINT CHECK”

switch and observe the reading on the display. With a
small screwdriver, adjust the Set Point trimmer (See
figure V.A.1) to above the reading observed in step

2. Release the “SET POINT CHECK” switch and observe

that the red “POOR” light is ON.

4.

Press the “SET POINT CHECK” switch and adjust screw
adjustment until the Set Point is below the reading
observed in step 2.

5.

Release the “SET POINT CHECK” switch and observe
that the green “ABOVE” light is ON. Also note the audible
click of the relay as the lights change.

6.

Readjust the Set Point adjustment to the desired Set
Point setting and replace front panel. This completes the

AQUASWITCH II

Monitor/controller Board checkout.

2 .

AQUASWITCH I

and

AQUASWITCH II

For

AQUASWITCH II

users, the term “Controller” refers to the

ASII

Monitor/controller Circuit Board functions.

1.

Turn the Purge Cycle trimmer adjustment screw fully
clockwise to obtain an approximate one minute cycle.
(See figure V.A.1)

2.

Adjust Controller “Set Point” to simulate “GOOD” water
quality (for the

AQUASWITCH II

, turn the Set Point

trimmer adjustment screw counterclockwise (see
Section IV.B.2 and See figure V.A.1 )) and verify the
following sequence of operation.

3.

Push “BANK SWITCH” several times to verify the
following Controller operations.
a.

Verify that the “IN USE” indicator lights switch ON
and OFF between Banks A and B each time “BANK
SWITCH” is pressed.

b.

Verify that both Banks A/B “GOOD” water quality
lights remain ON.

c.

Verify that the “BLEED” light remains OFF.

d.

Leave BANK A ON for next step. (If required, push
the “ALARM RESET” switch to reset alarm.)

NOTE: If the Logic Module Alarm Reset jumper has been
installed to provide the user with the optional Manual Bank Switch
alarm condition, the alarm will be activated each time the “BANK
SWITCH” is pressed. Otherwise, the alarm will be activated only
when the Purge Cycle time setting has expired. (Refer to Section
V.C)

4.

Adjust Controller Set Point to simulate “POOR” water

quality. (For the

AQUASWITCH II

, turn Set Point

trimmer adjustment screw clockwise, and verify the
following sequence of operation.)

a.

BANK A water quality indicates “POOR.”

b.

Yellow “BLEED” light turns ON and water is purged
from system. (This should continue for about 1
minute.)

c.

After 1 minute, BANK A will turn OFF and BANK B
will turn ON and indicate “POOR” water quality.

d.

After approximately 1 minute, BANK B should turn
OFF, the “BLEED” light should turn OFF, the Bleed

valve should close and the alarm should be
activated. The system is now entirely shut down.

NOTE: If an external alarm is connected, it will be activated when
the

AQUASWITCH

switches Banks. (Press the “ALARM

RESET” switch to turn OFF alarm.)

If an alarm is not connected, an alarm condition can be monitored
by connecting an ohm meter (DVM) across Power Board Alarm
Terminals COM and NO. The meter should indicate a CLOSED
CIRCUIT when in the alarm condition.

5.

Adjust the Controller Set Point to simulate “GOOD” water
quality. (For the AQUASWITCH II, turn Set Point trimmer
adjustment screw counterclockwise and verify the
sequence of operation.)

6.

Press the “BANK SWITCH.” The BANK A “IN USE” and
“GOOD” water quality indicator lights should turn ON.
Press the “BANK SWITCH” again and BANK B “IN USE”
and “GOOD” water quality indicator lights should turn
ON.

7.

Complete the following steps to return the

AQUASWITCH

to its normal operating status.

a.

Using the “BANK SWITCH,” select the desired Bank “IN
USE” status.

b.

Adjust the Controller “Set Point” to the desired minimum
water quality. (Refer to Section IV.B.2 and figure V.A.1. )

c.

Set Purge Cycle to the desired time delay. (Refer to
Section V.B)

REASSEMBLY

1. Carefully reinstall the front panel, bottom first. Ensure no

wires have been pinched between enclosure and front
panel.

2.

Reinstall the two (2) screws and tighten.

3.

To operate, turn power ON.