beautypg.com

1 process inlet/outlet connections – Pulsafeeder Polyfeeder EN User Manual

Page 10

background image

10

 

Supply water must be in the temperature range of 40 – 104 F (4.4 C to 40 C). Water should be filtered as
required to ensure that any particulate present is less than 5 microns in size, typically a 100 mesh screen is
recommended. It should also be noted that extremely hard water with adversely affect polymer solution
quality and increase usage of neat polymer.

 

6.3.1 Process Inlet/Outlet Connections

 

PolyFeeder process connections will vary depending on the maximum neat polymer flow rate of the
system, requiring more or less water flow.

 

Neat polymer flow rate

range

 

 

Neat Polymer Connection

Dilution Water Inlet

Solution outlet

Up to 3.0 GPH

1.0” FNPT

1.0” MNPT

 

0.5” FNPT

3.0 – 21 GPH

1.5” FNPT

1.5” MNPT

Above 21 GPH

2.0” FNPT

2.0” MNPT

Table 6-3-1 Process Water Inlet/Outlet for known Polymer Flow

 

 

 

 

Figure 6-3 Process Inlet and Output Locations