Electrical Requirements

M414038

48

© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT

Electrical Requirements

Refer to Table 10.

NOTE: Minimum wire sizes are obtained from
Canadian Electrical Code and are intended for use
as a guideline only. Electrical connections should be
made only by a qualified electrical contractor in
accordance with all applicable local and national
requirements.

NOTE: Connect to an individual branch circuit.

NOTE: Use copper conductors only.

Table 10

120 Pound Tumbler Model

Serial Plate Voltage

Terminal Block

Connections Required

Rated

Current*

Breaker

Rating

Breaker

Poles

Recommended

Wire Size

208 – 230V/60Hz/3ph

L1, L2, L3 and ground

6.7

10 Amps

3

14 AWG (2.6 mm

2

)

380 – 415V/50Hz/3ph

L1, L2, L3 and ground

4.7

10 Amps

3

14 AWG (2.6 mm

2

)

460 – 480V/60Hz/3ph

L1, L2, L3 and ground

4.0

10 Amps

3

14 AWG (2.6 mm

2

)

170 Pound Tumbler Model

Serial Plate Voltage

Terminal Block

Connections Required

Rated

Current

Breaker

Rating

Breaker

Poles

Recommended

Wire Size

208 – 230V/60Hz/3ph

L1, L2, L3 and ground

12.7

15 Amps

3

14 AWG (2.6 mm

2

)

380 – 415V/50Hz/3ph

L1, L2, L3 and ground

7.3

10 Amps

3

14 AWG (2.6 mm

2

)

460 – 480V/60Hz/3ph

L1, L2, L3 and ground

6.6

10 Amps

3

14 AWG (2.6 mm

2

)

* Current ratings vary slightly depending on model; refer to serial plate.