Red Lion PXU User Manual
Page 31
31
REGISTER
ADDRESS
REGISTER NAME
LOW LIMIT
HIGH LIMIT
FACTORY
SETTING
ACCESS
COMMENTS
LOCKOUT PARAMETERS
40101
Setpoint Access
0
4
0
Read/Write 0 = dISP, 1 = ParA, 2 = HIdE, 3 = LOC, 4 = dSPr
40102
Output 1 Power Access
0
4
1
Read/Write 0 = dISP, 1 = ParA, 2 = HIdE, 3 = LOC, 4 = dSPr
40103
Output 2 Power Access
0
4
1
Read/Write 0 = dISP, 1 = ParA, 2 = HIdE, 3 = LOC, 4 = dSPr
40104
Setpoint Ramp Rate Access
0
4
1
Read/Write 0 = dISP, 1 = ParA, 2 = HIdE, 3 = LOC, 4 = dSPr
40105
PID Group Access
0
4
1
Read/Write 0 = dISP, 1 = ParA, 2 = HIdE, 3 = LOC, 4 = dSPr
40106
Controller Status (Run/Stop) Access
0
4
0
Read/Write 0 = dISP, 1 = ParA, 2 = HIdE, 3 = LOC, 4 = dSPr
40107
Output Power Offset Access
1
3
1
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
40108
Proportional band Access
1
3
1
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
40109
Integral time Access
1
3
1
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
40110
Derivative time Access
1
3
1
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
40111
Integration Default Access
1
3
3
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
40112
Alarm 1 Value Access
1
3
1
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
40113
Alarm 2 Value Access
1
3
1
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
40114
Alarm 3 Value Access
1
3
1
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
40115
Alarm Reset Access
1
3
1
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
40116
Setpoint Select Access
1
3
1
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
40117
Auto-Tune Start Access
2
3
2
Read/Write 2 = HIdE, 3 = LOC
40118
Auto Control Mode Access
2
3
2
Read/Write 2 = HIdE, 3 = LOC
40119
Control Mode Transfer Access
2
3
2
Read/Write 2 = HIdE, 3 = LOC
40120
Deviation Value Access
0
3
0
Read/Write 0 = dISP, 3 = LOC
40121
Access Code
-125
125
0
Read/Write
0 = Full access to display, parameter, hidden, and
configuration loops; -1 to -125 = Code necessary to
access configuration loop only; 1 to 125 = Code
necessary to access hidden and configuration loops
ALARM PARAMETERS
40131
Alarm 1 Action
0
18
0
Read/Write
0 = No, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO,
5 = d-HI, 6 = d-Lo, 7 = b-In, 8 = b-ot, 9 = InPt,
10 = Ct1, 11 = Ct2, 12 = SOAK, 13 = r-UP,
14 = r-dn, 15 = rUn, 16 = HoLd, 17 = StoP, 18 = End
40132
Alarm 1 Annunciator
0
1
0
Read/Write 0 = Normal, 1 = Reverse
40133
Alarm 1 Reset Mode
0
1
0
Read/Write 0 = Automatic, 1 = Latched
40134
Alarm 1 Standby
0
1
0
Read/Write 0 = No, 1 = Yes
40135
Alarm 1 Value
-999
9999
100
Read/Write 1 = 1 Display unit
40136
Input Fail Alarm 1 Action
0
1
0
Read/Write 0 = Off; 1 = On
40137
Alarm 2 Action
0
18
0
Read/Write
0 = No, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO,
5 = d-HI, 6 = d-Lo, 7 = b-In, 8 = b-ot, 9 = InPt,
10 = Ct1, 11 = Ct2, 12 = SOAK, 13 = r-UP,
14 = r-dn, 15 = rUn, 16 = HoLd, 17 = StoP, 18 = End
40138
Alarm 2 Annunciator
0
1
0
Read/Write 0 = Normal, 1 = Reverse
40139
Alarm 2 Reset Mode
0
1
0
Read/Write 0 = Automatic, 1 = Latched
40140
Alarm 2 Standby
0
1
0
Read/Write 0 = No, 1 = Yes
40141
Alarm 2 Value
-999
9999
200
Read/Write 1 = 1 Display unit
40142
Input Fail Alarm 2 Action
0
1
0
Read/Write 0 = Off; 1 = On
40143
Alarm 3 Action
0
18
0
Read/Write
0 = No, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO,
5 = d-HI, 6 = d-Lo, 7 = b-In, 8 = b-ot, 9 = InPt,
10 = Ct1, 11 = Ct2, 12 = SOAK, 13 = r-UP,
14 = r-dn, 15 = rUn, 16 = HoLd, 17 = StoP, 18 = End
40144
Alarm 3 Annunciator
0
1
0
Read/Write 0 = Normal, 1 = Reverse
40145
Alarm 3 Reset Mode
0
1
0
Read/Write 0 = Automatic, 1 = Latched
40146
Alarm 3 Standby
0
1
0
Read/Write 0 = No, 1 = Yes
40147
Alarm 3 Value
-999
9999
300
Read/Write 1 = 1 Display unit
40148
Input Fail Alarm 3 Action
0
1
0
Read/Write 0 = Off; 1 = On
40149
Alarm Hysteresis
0
250(.0)° or
2500 (process)
0
Read/Write 1 = 1 Display unit; The same value applies to all
alarms.
40150
Change Color Intensity
0
4
0
Read/Write 0 = OFF, 1 = Any Alarm, 2 = AL-1, 3 = AL-2,
4 = AL-3