OP1 CYCLE TIME

.

to

.

seconds

OP2 CYCLE TIME

.

to

.

seconds

The Cycle Time is entered in seconds with one tenth of a second resolution.

It is the total time for one on and one off period of the OP1 time proportioning

control output. With time proportional control, the percentage of power is

converted into an output on-time relative to the cycle time value set. (If the

controller calculates that 65% power is required and a cycle time of 10.0

seconds is set, the output will be on for 6.5 seconds and off for 3.5 seconds.)

For best control, a cycle time equal to one-tenth or less, of the natural period of

oscillation of the process is recommended. When using the Analog Output

signal for control, the Cycle Time setting has no effect.

CONTROL ACTION

r = Reverse Acting

d = Direct Acting

A = Alarm 3

This determines the action for each Output. When programmed as

r1d2

,

Output 1 will function in the Reverse mode (heating) and Output 2 will function

in the Direct mode (Cooling). When selected as A, OP2 is configured as the

alarm 3 output and the alarm 3 settings will become accessible in the Alarm

module configuration menu and OP2 parameters will no longer be available.

OUTPUT 1 POWER LOWER LIMIT

.

to

.

%

This parameter may be used to limit controller power at the lower end due to

process disturbances or setpoint changes. Enter the safe output power limits for

the process. When the controller is in

USEr

or

OnOF

Control Mode or Auto Tune,

this limit does not apply.

OUTPUT 1 POWER UPPER LIMIT

.

to

.

%

This parameter may be used to limit controller power at the upper end due to

process disturbances or setpoint changes. Enter the safe output power limit for

the process. When the controller is in

USEr

or

OnOF

Control Mode, this limit

does not apply.

INPUT FAIL OP1 POWER LEVEL

This parameter sets the power level in the event of an input failure (open TC/

RTD or shorted RTD). Manual (

USEr

) Control overrides the input fail preset.

The Cycle Time is entered in seconds with one tenth of a second resolution.

It is the total time for one on and one off period of the OP2 time proportioning

control output. With time proportional control, the percentage of power is

converted into an output on-time relative to the cycle time value set. (If the

controller calculates that 65% power is required and a cycle time of 10.0

seconds is set, the output will be on for 6.5 seconds and off for 3.5 seconds.)

For best control, a cycle time equal to one-tenth or less, of the natural period of

oscillation of the process is recommended. When using Analog Output signal

for control, the Cycle Time setting has no effect.

7.2 mOdule 2 - O

uTpuT

p

arameTers

(

2-OP

)

OPAC

CYC1

CtrL

OP1L

OP1H

1F01

An1L

OP1 CYCLE

TIME

CONTROL

ACTION

CONTROL

MODE

OUTPUT 1

POWER

ANALOG LOW

SCALING

OUTPUT 1

INPUT

FAIL OP1

2-OP

CNFP

OP2L

ANALOG

HIGH SCALING

OUTPUT 1

TIME

OP2 CYCLE

An1H

CYC2

LOW LIMIT

HIGH LIMIT

POWER

OUTPUT 1

POWER LEVEL

OUTPUT 2

POWER

LOW LIMIT

P

P

IF02

gAN2

ON/OFF

CHYS

CONTROL

db-2

INPUT

FAIL OP2

POWER LEVEL

OUTPUT 2

DEADBAND

RELATIVE

GAIN

OUTPUT 2

HYSTERESIS

OP2H

POWER

HIGH LIMIT

OUTPUT 2

Programming/model dependent.

PARAMETER MENU

.

to

.

%

CONTROL MODE

Select the Control Output(s) mode of operation. This parameter can also be

selected in the Hidden Loop when configured in Module 3.

l

C

I



I

C

.

CC

.



.



.

I

.

CC

OUTPUT 1 ANALOG LOW SCALING

The output power level that corresponds with 0 V or 4 mA analog output.

.

to

.

.



OUTPUT 1 ANALOG HIGH SCALING

The output power level that corresponds with 10 V or 20 mA analog output.

An inverse action can be achieved by reversing the high and low scaling points.

.