background image

9

5.4 Module 4 - s

etpoint

o

utput

p

araMeters

(



)

PAR

Setpoint

Action

Setpoint

Select

Setpoint

Value

Output Reset

Action

Hysteresis

Value

Off Time

Delay

On Time

Delay

Output Reset

With Display

Reset

SPSEL

4-SPt

Act-n

SPt-n

HYS-n

tON-n

tOF-n

rSt-n

rEn-n

Pro

Standby

Operation

Stb-n

Enb-n

Setpoint

Enable

Probe

Burn-out

Action

brn-n

PARAMETER MENU

Select the Setpoint Output to be programmed, starting with Setpoint 1. The

” in the following parameters reflects the chosen Setpoint number. After the

selected setpoint is completely programmed, the display returns to



.

Repeat steps for Setpoint 2 if both Setpoints are being used. Select



to exit the

Setpoint programming module.

SETPOINT SELECT







Select



to enable Setpoint

and access the setup parameters. If



is

selected, the unit returns to



and Setpoint

is disabled.

SETPOINT ENABLE













Enter the action for the selected setpoint (output). See Setpoint Output

Figures for a visual detail of each action.

SETPOINT ACTION













High Acting, with balanced hysteresis
Low Acting, with balanced hysteresis
High Acting, with unbalanced hysteresis
Low Acting, with unbalanced hysteresis

=



=



=



=



OUTPUT

STATE

OFF

ON

Hys

SP + ½Hys

SP

SP - ½Hys

OFF

TRIGGER POINTS

High Acting (Balanced Hys) =



OUTPUT

STATE

OFF

ON

Hys

SP + ½Hys

SP

SP - ½Hys

OFF

TRIGGER POINTS

Low Acting (Balanced Hys) =



OUTPUT

STATE

OFF

ON

Hys

SP + Hys

SP

OFF

TRIGGER POINTS

Low Acting (Unbalanced Hys) =



OUTPUT

STATE

OFF

ON

Hys

SP

SP - Hys

OFF

TRIGGER POINTS

High Acting (Unbalanced Hys) =



SETPOINT VALUE

Enter the desired setpoint value. The decimal point position for the setpoint

and hysteresis values follow the selection set in Module 1.



to









HYSTERESIS VALUE

to



Enter desired hysteresis value. See Setpoint Output Figures for visual

explanation of how setpoint output actions (balanced and unbalanced) are

affected by the hysteresis. When the setpoint is a control output, usually

balanced hysteresis is used. For alarm applications, usually unbalanced

hysteresis is used. For unbalanced hysteresis modes, the hysteresis functions on

the low side for high acting setpoints and functions on the high side for low

acting setpoints.
Note: Hysteresis eliminates output chatter at the switch point, while time delay

can be used to prevent false triggering during process transient events.





OFF TIME DELAY



to



Sec

Enter the time value in seconds that the output is delayed from turning off

after the trigger point is reached. A value of 0.0 allows the meter to update the

output status per the response time listed in the Specifications.





ON TIME DELAY

Enter the time value in seconds that the output is delayed from turning on

after the trigger point is reached. A value of 0.0 allows the meter to update the

output status per the response time listed in the Specifications.



to



Sec

Enter the reset action of the output. See figure for details.



= Automatic action; This action allows the output to

automatically reset off at the trigger points per the Setpoint Action shown in

Setpoint Output Figures. The “on” output may be manually reset (off)

immediately by the front panel

RST

button or user input.The output remains

off until the trigger point is crossed again.

OUTPUT RESET ACTION









