Changing the communication settings – Vaisala WXT510 User Manual
Page 53

Chapter 6 ____________________________________________________ Communication Settings
VAISALA _______________________________________________________________________ 51
Changing the Communication
Settings
Make the desired setting with the following command. Select the
correct value/letter for the setting fields, see
Setting Fields on page 49
.
See also the examples.
Command format in ASCII and NMEA 0183:
aXU,A=x,M=x,C=x,I=x,B=x,D=x,P=x,S=x,L=x
Command format in SDI-12:
aXXU,A=x,M=x,C=x,I=x,B=x,D=x,P=x,S=x,L=x!
where
A, M, C, I,
B, D, P, S,L
=
The communication setting fields, see
Setting Fields
on page 49
.
x
=
Input value for the setting
=
Command terminator in ASCII and NMEA 0183
!
=
Command terminator in SDI-12
NOTE
When changing the serial interface and communication protocol, note
the following:
Each serial interface requires its specific wiring and/or jumper settings
described in
Chapter 5, Wiring and Power Management, on page 35
.
Change first the serial interface field C and then the communication
protocol field M.
Changing the serial interface to SDI-12 (C=1) will automatically
change the baud settings to 1200, 7, E, 1 and the communication
protocol to SDI-12 (M=S).
NOTE
Reset the transmitter to validate the changes of communication
parameters by disconnecting the service cable or using the Reset
(aXZ) command, see
Reset (aXZ) on page 53
.