5.1.6 Exercise
An Exercise time can be set by choosing a day of the week (Sun – Sat), a start time of day (12AM – 11:59PM), and a exercise
period (1 – 240 minutes). On the first occurrence of the chosen day of the week each month, at the programmed start time, the
generator will start and run for the programmed period.
ADV/MATE/AGS/EX----------
exstartday: --
DOWN AGS INC DEC
EXERCISE START DAY (exstartday):
This is the day of the week that the generator will start on. This can be set to
Mon – Fri, and Sat or Sun, depending on what day each month a generator
exercise period should be run. The setting “- -“ disables any exercise period.
MATE2M System Controller and Display User Manual
Copyright 2003
© OutBack Power Systems, Inc.
19009 62
nd
Ave NE, Arlington WA 98223 USA
Page 20
Rev 1.00 03/31/04 Tel 360 435 6030 Fax 360 435 6019
EX START TIME:
This setting controls at what time on the Exercise Start Day the generator will
start it’s exercise period. Press
settings.
ADV/MATE/AGS/EX----------
Ex start time: 12:00A
DOWN UP CHANGE
EX PERIOD:
ADV/MATE/AGS/EX----------
Ex period: 15 min
DOWN UP INC DEC
Ex Period is how long a generator exercise period will be.
can change the value between 1 – 240 minutes.