5.1.6 Exercise


An Exercise time can be set by choosing a day of the week (Sun – Sat), a start time of day (12AM – 11:59PM), and a exercise
period (1 – 240 minutes). On the first occurrence of the chosen day of the week each month, at the programmed start time, the
generator will start and run for the programmed period.

ADV/MATE/AGS/EX----------
exstartday: --

DOWN AGS INC DEC

EXERCISE START DAY (exstartday):

This is the day of the week that the generator will start on. This can be set to
Mon – Fri, and Sat or Sun, depending on what day each month a generator
exercise period should be run. The setting “- -“ disables any exercise period.


MATE2M System Controller and Display User Manual

Copyright 2003

© OutBack Power Systems, Inc.

19009 62

nd

Ave NE, Arlington WA 98223 USA

Page 20

Rev 1.00 03/31/04 Tel 360 435 6030 Fax 360 435 6019

EX START TIME:

This setting controls at what time on the Exercise Start Day the generator will
start it’s exercise period. Press to adjust the hour and minutes
settings.

ADV/MATE/AGS/EX----------
Ex start time: 12:00A

DOWN UP CHANGE


EX PERIOD:

ADV/MATE/AGS/EX----------
Ex period: 15 min

DOWN UP INC DEC

Ex Period is how long a generator exercise period will be. and
can change the value between 1 – 240 minutes.