Testing, System alarms, Front-panel system alarms summary – ADC HiGain H2TU-C-319 List 4E User Manual

Page 60: Esting, Ystem, Larms

background image

Testing

LTPH-UM-1049-02, Issue 2

52

January 9, 2002

H2TU-C-319 List 4E

T

ESTING

This section provides information about front-panel system alarms, LOS and AIS response, OCT55 test
procedure, and loopback testing.

S

YSTEM

A

LARMS

Table 21

summarizes all possible system alarms in order of priority as they appear on the front panel. When

multiple alarms occur, the front-panel display only reports the highest priority alarm. The alarm history screens
display alarms also, but provide greater detail (see

“Using the Performance Screens to View Alarm Data” on

page 44

). All alarms that are not inhibited will drive the front-panel Status LED to a flashing red alarm state.

Table 21.

Front-Panel System Alarms Summary

Front-Panel
Message

(a)

Alarm

Description

To Inhibit:

PWR FEED SHRT

(b)

Power Feed Short

A short exists between the Tip and Ring of the
HDSL2 pair.

Cannot be inhibited.

PWR FEED GND

(b)

Power Feed Ground

The HDSL2 loop is grounded.

Cannot be inhibited.

PWR FEED OPEN

(b)

Power Feed Open

A line power open condition exists.

Cannot be inhibited.

LOSW

(b)

Loss of Sync Word

(c)

The HDSL2 loop has lost synchronization.

Cannot be inhibited.

MTA

Metallic Test Access

The H2TU-C is in its MTA/LOSW test state.

Sets MTA option to disabled.

SPTE

Split Equipment

A test mode initiated by the HMU which splits the
AUX port’s DSX-1 payload and sends it to the MUX
port.

Sets ADS1 option to MUX or
CTHR.

SPTF

Split Facilities

A test mode initiated by the HMU which splits the
facility DS1 payload from the AUX port #1 and sends
it to the MUX port.

Sets ADS1 option to MUX or
CTHR.

LLOS

(b)

Local Loss of Signal

Loss of the DSX-1 input signal.

Cannot be inhibited.

RLOS

(b)

Remote Loss of Signal

Loss of the H2TU-R DS1 input signal.

Cannot be inhibited.

LAIS

Local Alarm Indication
Signal

Indicates an AIS (all ones) pattern is being received
at the H2TU-C input port.

Cannot be inhibited.

RAIS

Alarm Indication Signal
at the H2TU-R

Indicates an AIS (all ones) pattern is being received
at the H2TU-R DS1 input port.

Cannot be inhibited.

RRAI

Remote Alarm
Indication

Remote Alarm Indication at the H2TU-R Indicates an
RAI alarm (yellow LED) from the CPE with errors
from the line unit or network.

Cannot be inhibited.

LRAI

Remote Alarm
Indicator - Customer
Installation

Indicates an RAI alarm (yellow LED) from the CPE
with an error-free signal from the line unit or
network.

Cannot be inhibited.

TRCI

Remote Alarm
Indication - Customer
Installation

Upon reception of an RAI (yellow LED) from the
CPE, the H2TU-R sends RAI-CI toward the network
if the network signal received at the H2TU-R is clear.
If the network signal is impaired (LOS, AIS, or LOF),
then the RAI is passed on to the network unaltered.

Cannot be inhibited.

xxx-DBER

DS1 Bit Error Rate

The DS1 BER has exceeded the set 24-hour
threshold limit of approximately 10

-6

. (xxx denotes

either TUC or TUR. If TUC and TUR occur at the
same time, then TUC displays.)

Select DIS for the DBER
system option.

PRMF

Performance Report
Messaging - Far End

Indicates H2TU-R PRM-FE BER threshold is
exceeded.

Set DBER threshold to DIS.

PRMN

Performance Report
Messaging - Near End

Indicates H2TU-R PRM-NE BER threshold is
exceeded.

Set DBER threshold to DIS.

Continued