H2tu-r ds1 alarm history screen, Ds1 alarm descriptions, Table 17 on – ADC HiGain H2TU-C-319 List 4E User Manual
Page 53
LTPH-UM-1049-02, Issue 2
Monitoring System Activity and Performance
H2TU-C-319 List 4E
January 9, 2002
45
Figure 26.
H2TU-R DS1 Alarm History Screen
Table 17.
DS1 Alarm Descriptions
Screen Alarm
Front-Panel Alarm Description
)
SPTE
Split Equipment
A test mode initiated by the HMU which splits the AUX port’s DSX-1 payload and sends it to the
MUX port.
SPTF
Split Facilities
A test mode initiated by the HMU which splits the AUX facility DS payload from the AUX port
#1 and sends it to the MUX port.
LLOS
(a)
LLOS
Local Loss of Signal—Loss of the H2TU-C DSX-1 input signal.
LAIS
LAIS
Line Alarm Indication Signal—Indicates an AIS (all ones) pattern is being detected at the
H2TU-C DS1 input port. The ALMP option determines whether AIS (default) or LOS is sent
towards the CPE.
DBER
xxx-DBER
Bit Error Rate—The DS1 BER has exceeded the built-in 24-hour threshold limits of
approximately 10
-6
. (xxx denotes either TUC or TUR.)
above)
RLOS
(a)
RLOS
Remote Loss of Signal— Loss of the H2TU-R DS1 input signal.
RAIS
RAIS
Remote Alarm Indication Signal—AIS is being detected at the H2TU-R DS1 input port. By
default (see
) AIS-CI
(b)
is sent toward the network.
RAI
RRAI
Remote Alarm Indication—Indicates an RAI alarm (yellow) from the CPE with errors from the
line unit or network.
TX RAI-CI
TRCI
Transmit RAI-CI - Remote Alarm Indication at the H2TU-R—Upon reception of an RAI (yellow
LED) from the CPE, the H2TU-R sends an RAI-CI towards the network if the network signal
received at the H2TU-R is clear. If the network signal is impaired (LOS, AIS or LOF), then the
RAI is passed on to the network unaltered. This is applicable to SF or ESF framing. In an all SF
environment, RACI must be enabled to convert SF-RAI to SF-RAI-CI.
PRM-NE
PRMN
Performance Report Monitoring - Near End—The count of the PRM-NE register at the H2TU-R
exceeds the 10
-6
BER threshold at 648 events since 12:00:00 AM.
PRM-FE
PRMF
Performance Report Monitoring - Far End—The count of the PRM-FE register at the H2TU-R
exceeds the 10
-6
BER threshold at 648 events since 12:00:00 AM.
Continued
Monitor
Performance
Event Log
Config
Inventory
Report
Rlogon
Help
H2TU-R DS-1 Alarm History
-----------------------------------------------------------------------------
Alarm
First
Last
Status
Count
RLOS
OK
0
RAIS
OK
0
RAI
OK
0
TX RAI-CI
OK
0
PRM-NE
OK
0
PRM-FE
OK
0
DBER
08/16/01 00:37
08/16/01 00:45
OK
7
Press: C(l)ear Alarm History
------------------------------------------------------------------------------
Use
Interface
:
H2TU-R DS-1
choices and
Statistics :
Alarm History
ID: xxxx--xxxx--xxxx--xxxx
08/01/2001 07:05:33
H2TU-C
System: Alarm