Note: the open circuit window (between 350µA and 50µA) is not
hysteresis, all MTL5000 Series modules with inputs conforming to
NAMUR/DIN 19234 will switch between open and complete circuit
conditions within these limits.
Note: the short circuit window (between 100

Ω

and 360

Ω

) is not

hysteresis, all MTL5000 Series modules with inputs conforming to
NAMUR/DIN 19234 will switch between open and complete circuit
conditions within these limits.
Modules with LFD and inputs conforming to NAMUR/DIN
19234:
MTL5011B, 5014* and 5018: LFD enable switch on top label

* The MTL5014 has a Slave/LFD output relay arrangement
(see module description in section 6).
MTL5012 and 5015: LFD enable switch on top label

MTL5017: LFD permanently enabled

Other modules with LFD facility
MTL5023 solenoid/alarm driver: LFD automatic

MTL5046 isolating driver: LFD automatic

Note: The safe-area circuit impedance will increase with hazardous-
area load and will rise >150k

Ω for the 'open circuit' line fault.

MTL5113x: LFD automatic

Hazardous-area load

Safe-area input

<50

Ω

High impedance (>150k

Ω)

>90

Ω

Normal operation

Hazardous-area input (either channel)

Line-fault-detect relay

<50µA

De-energised

>350µA

Energised

>360

Ω

Energised

<100

Ω

De-energised

LFD switch setting

Hazardous-area input(s)

Solid-state output(s)

On

<50µA

Non-conducting

On

>350µA

Conducting

On

>360

Ω

Conducting

On

<100

Ω

Non-conducting

LFD switch setting

Hazardous-area input(s)

Output relay(s)

On

<50µA

De-energised

On

>350µA

Energised

On

>360

Ω

Energised

On

<100

Ω

De-energised

3.1.3

Phase reversal

Switch(es) to change the phase of the output(s) relative to the input(s) are
provided on the top labels of some of the MTL5000 Series modules and
on the base of others. The following applies:
MTL5011B, 5014 and 5018: Phase reversal switch on top label

MTL5017: Phase reversal switch on base of module

MTL5012 and 5015: Phase reversal switch on top label

MTL5023 and 5024: Phase reversal switch on base of module

Positions for base-located switches are set as shown in figure 3.4.

3.1.4

Line fault detection (LFD)

Line fault detection on hazardous-area sensor lines (open circuit or short
circuit) is provided on some MTL5000 Series modules.
Note: resistors must be fitted when using the LFD facility with a contact
input: 500

Ω

to 1k

Ω

in series with switch and 20k

Ω

to 25k

Ω

in parallel

with switch.
For hazardous-area inputs conforming to NAMUR/DIN
19234, a line fault condition is indicated as follows:
Open circuit condition if hazardous-area current <50µA
Line integrity (no open circuit) if hazardous-area current >350µA
Short circuit condition if hazardous-area load <100

Ω

Line integrity (no short circuit) if hazardous-area load >360

Ω

A

B

2

1

Normal

Reverse

CH1

CH2

Label face

Base of unit

3

INM5000-6 Jul 2010

PR switch setting

Hazardous-area input(s)

Output relay(s)

Off

<1.2mA

De-energised

Off

>2.1mA

Energised

On

<1.2mA

Energised

On

>2.1mA

De-energised

PR switch setting

Hazardous-area input(s)

Solid-state output(s)

Off

<1.2mA

Non-conducting

Off

>2.1mA

Conducting

On

<1.2mA

Conducting

On

>2.1mA

Non-conducting

Hazardous-area

PR switch setting

Safe-area control

output

o

← (off)

CTRL+Ve >4.5V above CTRL-Ve

Enabled

o

← (off)

CTRL+Ve <1.4V above CTRL-Ve

Disabled

→ + (on)

CTRL+Ve >4.5V above CTRL-Ve

Disabled

→ + (on)

CTRL+Ve <1.4V above CTRL-Ve

Enabled

Hazardous-area load

Solid-state LFD output

<50

Ω

Non-conducting

>7k

Ω

Non-conducting

Hazardous-area input

LFD output

< 50µA (open-circuit)

de-energised

> 6.6mA (short-circuit)

de-energised

Figure 3.4: Phase reversal switch on base of units

PR switch setting

Hazardous-area input(s)

Output relay(s)

o

← (off)

<1.2mA

De-energised

o

← (off)

>2.1mA

Energised

→ + (on)

<1.2mA

Energised

→ + (on)

>2.1mA

De-energised