Dwyer MTL5045 User Manual

Page 17

background image

6.3.3

Testing

Make the safe- and hazardous-area connections shown in figure 6.6
and check as shown in table 6.2

6.4

MTL5014 single-pole changeover
relay single-channel dual-output
switch/proximity detector with line
fault detection and phase reversal

The MTL5014 enables two safe-area loads to be relay-controlled by a
single hazardous-area switch or proximity detector. Phase reversal (see
3.1.3 and figure 6.8), line fault detection and slave/line fault monitoring
configurations are possible.

6.4.1

Wiring connections

See figure 6.7 for wiring connections
Note: Reactive loads must be adequately suppressed.

13

INM5000-6 Jul 2010

6.3.1

Wiring connections

See figure 6.5 for wiring connections.

6.3.2

Line fault detection

(See section 3.1.4 for definition of a line fault)
Input line faults (open- or short-circuit) are indicated by an LED and the
non-conducting of the output. LFD is enabled/disabled by a switch
located on top of the module. Note that if the LFD facility is enabled for
switch inputs, the resistors shown in figures 6.5 and 6.6 MUST be fitted.

Table 6.2

Terminal

Function

1

Input –ve

2

Input +ve

3

Earth leakage detection

10 &11

Output –ve

12

Output +ve

13

Supply –ve

14

Supply +ve

–

+

6

5

4
3

2

1

7

8

9

10

11

12

13

14

Vs–

Vs+

20 to 35V dc

To earth

leakage

detector

SW

22kW

680W

a

b

c

+

–

1kW

V

d

Phase

Input

Output

Channel

Line fault

reverse

Line fault

switch

status

status LED

LED

switch

detection

(SW)

(11-12)

(yellow)

(red)

Normal

Off

a

V

d

< 4V

On

Off

Reverse

Off

I

sc

= 7–9mA

V

d

= V

S

Off

Off

Reverse

Off

Open

V

d

< 4V

On

Off

Normal

On

V

oc

= 7V5–9V5

V

d

= V

S

Off

On

Normal

On

a

V

d

= V

S

Off

On

Normal

On

c

V

d

< 4V

On

Off

Normal

On

b

V

d

= V

S

Off

Off

Terminal

Function

1

Input –ve

2

Input +ve

3

Earth leakage detection

7

Normally closed (output 2)

8

Common (output 2)

9

Normally open (output 2)

10

Normally closed (output 1)

11

Common (output 1)

12

Normally open (output 1)

13

Supply –ve

14

Supply +ve

Figure 6.6: Test circuit for MTL5012

–

+

6

5

4
3

2

1

7

8

9

10

11

12

13

14

Vs–

Vs+

20 to 35V dc

To earth

leakage

detector

22kW

680W

+

–

Resistors required only

for line fault detection

Figure 6.5: MTL5012 wiring diagram and connections

Hazardous area

Safe area

6

5

4
3

2

1

7

8

9

10

11

12

13

14

Vs–

Vs+

20 to 35V dc

To earth

leakage

detector

22kW

680W

+

–

Output 2

Output 1

For contact inputs

resistors must be fitted

Figure 6.7: MTL5014 wiring diagram and connections

Safe area

Hazardous area