Table 6.4

6.5.2

Line fault detection

(See section 3.1.4 for definition of a line fault)
On both channels, input line faults (open- or short-circuit) are indicated
by an LED and the de-energising of the output. LFD is enabled/disabled
by switches located on top of the module. Note that if the LFD facility is
enabled for switch inputs, the resistors shown in figures 6.10 and 6.11
MUST be fitted.

6.5.3

Testing

Make the safe- and hazardous-area connections shown in figure 6.11
and check the status of the output contacts for each channel in turn (with
a 22k

Ω resistor connected to the other channel) as shown in table 6.4.

6.6

MTL5016 single-pole relay two-
channel switch/proximity detector
with phase reversal (Discontinued,
use MTL5018)

The MTL5016 enables two safe-area loads to be relay-controlled by two
switches or proximity detectors located in a hazardous area. Output
phase reversal (see 3.1.3) is provided.

Table 6.5

6.6.1

Wiring connections

See figure 6.12 for wiring connections.
Note: Reactive loads must be adequately suppressed.

6.6.2

Testing

Make the safe- and hazardous-area connections shown in figure 6.13
and check status LEDs and relay contacts as in table 6.5.

6.7

MTL5017 single-pole relay two-
channel switch/proximity detector
with line fault detection and phase
reversal

The MTL5017 is similar to the MTL5018 but with the addition of line fault
detection facilities.

6.7.1

Wiring connections

See figure 6.14 for wiring connections.
Note: Reactive loads must be adequately suppressed.

6.7.2

Line fault detection

(

See section 3.1.4 for definition of a line-fault)

Line faults de-energise a dedicated line fault detect relay (between
terminals 7 and 10) to provide an alarm facility and are indicated by an
LED. Each channel relay will also de-energise (open) when a line fault
exists on that channel. LFD is automatic. Note that for switch inputs the
resistors shown in figures 6.14 and 6.15 MUST be fitted for correct LFD
operation.

Phase

Input

Output

Channel

Line fault

reverse

Line fault

switch

status

status LED

LED

switch

detection

(SW)

(11-12, 8-9)

(yellow)

(red)

Normal

Off

a

V

d

<4V

On

Off

Reverse

Off

a

V

d

=V

S

Off

Off

Reverse

Off

open

V

d

<4V

On

Off

Normal

On

open

V

d

=V

S

Off

On

Normal

On

a

V

d

=V

S

Off

On

Normal

On

c

V

d

<4V

On

Off

Normal

On

b

V

d

=V

S

Off

Off

Phase reverse Phase reverse

Channel 1

Channel 2

Relay

Relay

Input switch

Input switch

switch

switch

status LED

status LED

contacts

contacts

(ch 1)

(ch 2)

(ch 1)

(ch 2)

(yellow)

(yellow)

(ch 1)

(ch 2)

Closed

Open

Normal

Normal

On

Off

Closed

Open

Closed

Closed

Normal

Normal

On

On

Closed

Closed

Closed

Closed

Reverse

Reverse

Off

Off

Open

Open

Open

Open

Reverse

Reverse

On

On

Closed

Closed

Terminal

Function

1

Input –ve (Ch 1)

2

Input +ve (Ch 1)

3

Earth leakage detection

4

Input –ve (Ch 2)

5

Input +ve (Ch 2)

8

Output (Ch 2)

9

Output (Ch 2)

11

Output (Ch 1)

12

Output (Ch 1)

13

Supply –ve

14

Supply +ve

3
2
1

6
5
4

7
8
9

10
11
12

13
14

Vs–
Vs+

20 to 35V dc

+

–

SW1

SW2

Ch1

Ch2

+

–

Figure 6.13: Test circuit for MTL5016

3
2
1

6
5
4

7
8
9

10
11
12

13
14

Vs–
Vs+

20 to 35V dc

+

–

To earth leakage

detector

Ch1

Ch2

Ch1

Ch2

+

–

Figure 6.12: MTL5016 wiring diagram and connections