MTL5022 loop-powered
solenoid/alarm driver, IIB

The MTL5022 enables a device located in the hazardous area to be
controlled by a switch located in the safe area. Suitable for IIA and IIB
applications.

6.11.1

Wiring connections

See figure 6.22 for wiring connections.

6.11.2

Testing

Make the safe- and hazardous-area connections shown in figure 6.23,
apply 24V to terminals 11 and 12 and, with no load, check voltage and
short-circuit current levels at terminals 1 and 2 as follows

18

INM5000-6 Jul 2010

6.12

MTL5023 solenoid/alarm driver with
line fault detection and phase reversal

The MTL5023 enables a device located in the hazardous area to be
controlled by a volt-free contact or logic signal located in the safe area.
Line fault detection (LFD) and output phase reversal (see 3.1.3) facilities
are included.

6.12.1

Wiring connections

See figure 6.24 for wiring connections.

6.12.2

Line fault detection

(See section 3.1.4 for definition of a line fault)
Hazardous-area line faults are signalled to the safe area by an LED and
a solid-state switch which de-energises when a line is open- or short-
circuited.

6.12.3

Testing

Make the safe- and hazardous-area connections shown in figure 6.25
and carry out the voltage and current checks as shown in table 6.8.

Input

Status

Output

Short-circuit

voltage

LED

voltage

current

(terminals 11 & 12) yellow (terminals 1 & 2)

(terminals 1 & 2)

24V dc

On

22 to 24V

24V dc

On

61 to 70mA

Terminal

Function

1

Output –ve

2 Output

+ve

3

Earth leakage detection

11

Supply –ve

12

Supply +ve

7
8
9

10
11
12

6
5
4

3
2
1

24Vdc

–
+

+

–

V

A

Figure 6.23: Test circuit for MTL5022

7
8
9

10
11
12

6
5
4

3
2
1

Solenoid, alarm or

other IS device

To earth

leakage

detector

20 – 35Vdc

–
+

+

–

Hazardous area

Safe area

Figure 6.22: MTL5022 wiring diagrm and connections

Input switch

LFD

Status

Output

Output

SW1

Phase reverse

LED

LED

voltage

current

(terminals 11 & 12)

Load

switch

(red)

(yellow)

(terminals 1 & 2)

(terminals 1 & 2)

Closed

2k

Ω

Normal

Off

On

>19.5V

Open

2k

Ω

Normal

Off

Off

<4.5V

Closed

15k

Ω

Normal

On

On

>21.0V

Open

15k

Ω

Normal

On

Off

<7.0V

Closed

Short-circuit

Normal

On

On

>45mA

Open

Short-circuit

Normal

On

Off

<6mA

Closed

Short-circuit

Reverse

On

Off

<6mA

Table 6.8

Vs–
Vs+

20 to 35V dc

Line fault

detection

+

–

+

–

Test meter

(set initially

to volts)

Load

+

–

6
5
4

3
2
1

7
8
9

10
11
12

13
14

Solenoid, alarm or

other IS device

To earth

leakage

detector

+

–

Vs–
Vs+

20 to 35V dc

Line fault
detection

+

–

+

–

6
5
4

3
2
1

7
8
9

10
11
12

13
14

Figure 6.24: MTL5023 wiring diagram and connections

Figure 6.25: Test circuit for MTL5023

Hazardous area

Safe area

Terminal

Function

1

Output –ve

2

Output +ve

3

Earth leakage detection

7

Line fault signal -ve

10

Line fault signal +ve

11

Control –ve

12

Control +ve

13

Supply –ve

14

Supply +ve