6.13

MTL5024 solenoid/alarm driver,
logic drive with phase reversal

The MTL5024 enables an on/off device located in a hazardous area to
be controlled by a volt-free contact or logic signal located in t he safe
area. Output phase reversal (see 3.1.3) facilities are included.

6.13.1

Wiring connections

See figure 6.26 for wiring connections.

6.13.2 Testing
Make the safe- and hazardous-area connections shown in figure 6.27
and carry out the following output voltage and short-circuit current
checks:

6.14

MTL5025 low-current loop-powered
solenoid/alarm driver, IIC

The MTL5025 enables an on/off device located in a hazardous area to
be controlled by a switch or voltage change in a safe area.

6.14.1

Wiring connections

See figure 6.28 for wiring connections.

19

INM5000-6 Jul 2010

6.14 .2

Testing

Make the safe- and hazardous-area connections shown in figure 6.29
and carry out the following output voltage and short-circuit current
checks:

6.15

MTL5031 vibration transducer
interface

The MTL5031 repeats the signal from a vibration sensor in a hazardous
area to a monitoring system in a safe area.

6.15.1 Wiring connections
See figure 6.30 for wiring connections.

Terminal

Function

1

Output –ve

2

Output +ve

3

Earth leakage detection

11

Control –ve

12

Control +ve

13

Supply –ve

14

Supply +ve

Solenoid, alarm or

other IS device

To earth

leakage

detector

+

–

Vs–
Vs+

20 to 35V dc

+

–

Control

6
5
4

3
2
1

7
8
9

10
11
12

13
14

Figure 6.26: MTL5024 wiring diagram and connections

SW1

Output

Output

(terminals

Phase

Status

voltage

current

11 & 12)

setting

LED

(terminals1 & 2)

(terminals 1 & 2)

Closed

Normal

On

22 to 24V

Closed

Normal

On

45 to 52mA

Closed

Reverse

On

<6mA

Vs–
Vs+

20 to 35V dc

+

–

+

–

SW1

V

A

6
5
4

3
2
1

7
8
9

10
11
12

13
14

Figure 6.27: Test circuit for MTL5024

Safe area

Hazardous area

Terminal

Function

1

Output –ve

2

Output +ve

3

Earth leakage detection

11

Supply –ve

12

Supply +ve

Solenoid, alarm or

other IS device

To earth

leakage

detector

+

–

20 to 35V dc

+

–

6
5
4

3
2
1

7
8
9

10
11
12

Figure 6.28: MTL5025 wiring diagram and connections

Input voltage

Status

Output voltage

Output current

(terminals 11 & 12)

LED

(terminals 1 & 2)

(terminals 1 & 2)

24V

On

22 to 24V

24V

On

45 to 52mA

+

–

20 to 35V dc

+

–

V

A

6
5
4

3
2
1

7
8
9

10
11
12

Figure 6.29: Test circuit for MTL5025

Hazardous area

Safe area

Vs–
Vs+

20 to 35V dc

Vibration

transducer

Common

Signal

Transducer

power V

T

Signal –ve

Signal 0V

Monitor

6
5
4

3
2
1

7
8
9

10
11
12

13
14

Figure 6.30: MTL5031 wiring diagram and connections

Hazardous area

Safe area

Terminal

Function

1

Common

2

Signal

3

Transducer power V

T

11

Signal –ve

12

Signal 0V

13

Supply –ve

14

Supply +ve