6.9.3

Testing

Make the safe- and hazardous-area connections shown in figure 6.19,
and check the status of the output contacts for each channel in turn (with
a 22k

Ω resistor connected to the other channel) as shown in table 6.7.

6.10

MTL5021 loop-powered
solenoid/alarm driver, IIC

The MTL5021 enables a device located in the hazardous area to be
controlled by a switch located in the safe area. Suitable for IIC
applications.

610.1

Wiring connections

See figure 6.20 for wiring connections.

6.10.2

Testing

Make the safe- and hazardous-area connections shown in figure 6.19,
apply 24V to terminals 11 and 12 and, with no load, check voltage and
short-circuit current levels at terminals 1 and 2 as follows:

Terminal

Function

1

Input –ve (Ch 1)

2

Input +ve (Ch 1)

3

Earth leakage detection

4

Input –ve (Ch 2)

5

Input +ve (Ch 2)

6

Earth leakage detection

7

Normally-closed contact (Ch 2)

8

Common (Ch 2)

9

Normally-open contact (Ch 2)

10

Normally-closed contact (Ch 1)

11

Common (Ch 1)

12

Normally-open contact (Ch 1)

13

Supply N

14

Supply L

6

5

4
3

2

1

7

8

9

10

11

12

13

14

680W

22kW

22kW

To earth leakage

detector

SW

a

b

c

open

+

–

Ch1

Ch2

Vs
Vs

85 to 265V ac

Ch1

Ch 2

+

–

Phase

Input

Output

Output

Channel

Line fault

reverse

Line fault

switch

relay

relay

status LED

LED

switch

detection

(SW)

(11-12, 8-9)

(10-11, 7-8)

(yellow)

(red)

Normal

Off

a

Closed

Open

On

Off

Reverse

Off

I

sc

= 7 – 9mA

Open

Closed

Off

Off

Reverse

Off

Open

Closed

Open

Off

Off

Normal

On

V

oc

= 7.5 – 9.5V

Open

Closed

Off

On

Normal

On

a

Open

Closed

Off

On

Normal

On

b

Open

Closed

Off

Off

Normal

On

c

Closed

Open

On

Off

Input

Output

Short-circuit

voltage

Status

voltage

current

(terminals 11 & 12)

LED

(terminals 1 & 2) (terminals 1 & 2)

24V dc

On

22 to 24V

24V dc

On

45 to 52mA

Figure 6.19: Test circuit for MTL5018AC

6

5

4
3

2

1

7

8

9

10

11

12

13

14

Vs
Vs

85 to 265V ac

Ch1

Ch 2

+

–

22kW

22kW

680W

+

–

To earth

leakage

detector

Ch 1

Ch 2

680W

Hazardous area

Safe area

Figure 6.18: MTL5018AC wiring diagram and connections

7
8
9

10
11
12

6
5
4

3
2
1

Solenoid, alarm or

other IS device

To earth

leakage

detector

20 – 35Vdc

–
+

+

–

Hazardous area

Safe area

Figure 6.20: MTL5021 wiring diagram and connections

Table 6.7

7
8
9

10
11
12

6
5
4

3
2
1

24Vdc

–
+

+

–

V

A

Figure 6.21: Test circuit for MTL5021

Terminal

Function

1

Output –ve

2

Output +ve

3

Earth leakage detection

11

Supply –ve

12

Supply +ve