MTL5991 24V dc power supply

The MTL5991 provides a convenient source of power for MTL5000
Series units in locations where a dc supply is not readily available. The
2A capability at 24V dc is sufficient to drive at least fifteen (15)
MTL5000 Series modules, or more in appropriate combinations (see
table 6.16), and the wide mains power supply range makes this unit
universally applicable.
Table 6.16

Note:The maximum current drawn from the load unit is taken at 24V.
The maximum current drawn from the MTL5991 was taken to be 1.6A

6.35.1

Wiring connections

See figure 6.80 for wiring connections.

32

INM5000-6 Jul 2010

Current

MTL5000 unit

Drawn mA

Maximum

(Vs=24V)

number of units

MTL5011B

35

46

MTL5012

30

53

MTL5014

45

36

MTL5015

44

36

MTL5017

50

32

MTL5018

60

27

MTL5023

100

16

MTL5024

100

16

MTL5031

80

20

MTL5032

65

25

MTL5040

95

17

MTL5041

70

23

MTL5042

75

21

MTL5044

110

15

MTL5045

50

32

MTL5046

65

25

MTL5048

40

35

MTL5049

65

25

MTL5051

90

18

MTL5074

68

24

MTL5081

20

80

MTL5082

55

29

MTL5113P

70

23

MTL5314

85

19

MTL5344

122

13

MTL5349

67

24

WARNING

Segregation between hazardous- and safe-area wiring
must always be maintained

4
5
6
7
8

+

–

1
2
3

Figure 6.80: MTL5991 wiring diagram and connections

Terminal

Function

1

AC Line

2

Earth

3

AC neutral

4

+24V

5

+24V

6

OV

7

OV

8

Do not use

Safe area

6.35.2

Testing

Using the terminal assignments shown in figure 6.81, make the following
tests and checks.
1. Connect a supply voltage of between 85V and 264V ac to the

live and neutral terminals. Check that the voltage measured
across these terminals is within the range 85V to 264V ac.

2

With no load connected to the unit's output, measure, in turn, the
voltage between terminals 4 and 6 then 5 and 7. Check that the
measurements are in the range 23.64V to 24.36V.

3

Connect to the output, a load that draws up to 2A from a supply
voltage between 105V and 264V ac, and draws 1.7A when the
supply voltage is less than 105V ac. Measure, in turn, the voltage
across terminals 4 and 6 and 5 and 7. Check that these
measurements are in the range 23.64V to 24.36V with a ripple
not greater than 100mV.

6.36

MTL5995 fieldbus power supply for
31.25kbit/s fieldbuses

The MTL5995 is a general purpose power supply unit designed for use
in 31.25kbit/s (H1) fieldbus systems. The MTL5995 complies with the
requirements of Fieldbus Foundation™ power supply Type 131 (non-IS
supply intended for feeding an IS barrier).).
To allow adequate heat dissipation under all likely thermal conditions, it
is recommended that MTL5995s are installed on DIN rail with a 10mm
space between adjacent units. MTL MS010 10mm DIN-rail module
spacers are available for this purpose (see section 4.2.1).
To comply with fieldbus standards, each bus must be terminated at both
ends. MTL's FBT1-IS or FCS-MBT fieldbus terminators (see section 6.37)
can be supplied for this purpose or, for installations in which the
MTL5995 is located at one end of the fieldbus trunk, it includes an
internal terminator which is enabled by a yellow switch (B) located on
the base of the unit (see figure 6.82). A second, red switch (A) in the
base of the unit should be kept in the normal mode position.

(For network and termination criteria, see applicable fieldbus standards
and specification

IEC 61158-2, ISA-S50.02 for 31.25kbit/s fieldbus

systems, Foundation™ Fieldbus 31.25kbit/s Physical Layer Profile
Specification FF-816 and MTL's Application Brief AB001.)

4
5
6

L

E

N

7
8

+

–

Figure 6.81: Terminal assignments for MTL5991

A

B

2

1

NORMAL MODE SW1

TERMINATOR OUT SW2

NOT USED

Red

Yellow

TERMINATOR IN

Label face

Base of unit

Figure 6.82: Functions of switches on the base of an MTL5995