MTL5344 Repeater power supply

The MTL5344 provides fully-floating dc supplies for two conventional 2-
wire 4 to 20mA transmitters located in a hazardous area and repeats
the current in two floating circuits to drive two safe-area loads.
Note that although this module is similar in function to the MTL5044, the
safety description parameter are very different. Refer to the datasheet
and the ATEX certificate available from the MTL website.

6.33.1

Wiring connections

See figure 6.76 for wiring connections.

6.33.2

Testing

Make the safe- and hazardous-area connections shown in figure 6.77
and, using RV1 to vary the output current, carry out the following checks,
first on channel 1 and then on channel 2:

6
5
4
3
2
1

7
8
9

10
11
12

13
14

I

I

I

I

Ch 2

Ch 1

Vs–
Vs+

20 to 35V dc

–

4/20mA

Load

+

–

4/20mA

Load

+

+

–

4/20mA

+

–

4/20mA

Ch 2

Ch 1

Figure 6.76: MTL5344 wiring diagram and connections

Hazardous area

Safe area

Terminal

Function

1

Input –ve (Ch 1)

2

Input +ve (Ch 1)

4

Input –ve (Ch 2)

5

Input +ve (Ch 2)

8

Output –ve (Ch 2)

9

Output +ve (Ch 2)

11

Output –ve (Ch 1)

12

Output +ve (Ch 1)

13

Supply -ve

14

Supply +ve

7
8
9

6
5
4
3
2
1

13
14

10
11
12

I

I

I

I

–

+
–

+

Ch 1

10kW lin

RV1

A1

A2

Ch 1

Ch 2

Ch 2

Vs–
Vs+

20 to 35V dc

–

+

–

+

Figure 6.77: Test circuit for MTL5344

Output

Current

Voltage channel 1

Voltage channel 2

current

reading

(terminal 2 with

(terminal 5 with

(A2)

(A1)

respect to terminal 1)

respect to terminal 4)

4 to 20mA

<±20µA

20ma

>14V

20ma

>14V

6.34

MTL5349 two-channel isolating driver

The MTL5349 isolates and passes on two 4 to 20mA signals from a
controller located in a safe area to two loads in a hazardous area.
Note that although this module is similar in function to the MTL5049, the
safety description parameter are very different. Refer to the datasheet
and the ATEX certificate available from the MTL website.

6.34.1

Wiring connections

See figure 6.78 for wiring connections.

6.34.2

Testing

Make the safe- and hazardous-area connections shown in figure 6.79
and, using the current source to vary the output current, carry out the
following checks, first on channel 1 and then on channel 2.

6
5
4
3
2
1

7
8
9

10
11
12

13
14

I

I

I

I

P

I

4/20mA

+

–

P

I

4/20mA

+

–

–

+

4/20mA

–

+

4/20mA

Vs–
Vs+

20 to 35V dc

Ch 1

Ch 2

Ch 1

Ch 2

Figure 6.78: MTL5349 wiring diagram and connections

Hazardous area

Safe area

Terminal

Function

1

Output –ve (Ch 1)

2

Output +ve (Ch 1)

4

Output -ve (Ch 2)

5

Output +ve (Ch 2)

8

Input -ve (Ch 2)

9

Input +ve (Ch 2)

11

Input –ve (Ch 1)

12

Input +ve (Ch 1)

13

Supply –ve

14

Supply +ve

Output

Current

current

reading (A1)

4 to 20mA

<±20

μA

6
5
4
3
2
1

7
8
9

10
11
12

13
14

I

I

I

I

Vs–
Vs+

20 to 35V dc

A1

A2

–

+

Current

source

470W

+

–

+

–

+

Ch1

Ch2

Ch1

Ch2

Figure 6.79: Test circuit for MTL5349