beautypg.com

Dwyer GFT2 User Manual

Page 6

background image

Submenu “User-Defined Units”
In addition to conventional flow units, user-defined flow engineering units may be
selected. Use the “Engineering Units and K-Factor Menu” to navigate to the “User
Defined Units” menu option. This option enables user-defined configuration of any
engineering unit required for process measurement.

The following three parameters are available for this function:
1. UD Unit volume K-Factor (defined in Liters)
2. UD Unit time base (defined in Seconds)
3. UD Unit use density (units with or without density support)

Before using User-Defined Unit, make sure the proper conversion factor of the new
unit with respect to one liter is set (the default entry is 1.00 Liter). Also, proper time
base values for User-Defined Units must be set.

The following selections are available: 1 second, 60 seconds (1 minute), 3600
seconds (1 hour), 86400 seconds (1 day). The default entry is 60 seconds. If a
mass based User-Defined Unit is desired, then “UD Unit Use Density” parameter
must be set to “YES”. The default entry is “NO”, so Fluid STD Density parameter is
not used for flow rate calculation.

Submenu “K-Factors Settings”
Conversion factors relative to Nitrogen are convenient to use when flow
meter/controller mated to GFT2 is calibrated for Nitrogen and another gas is
required to be measured/controlled.

Conversion factors relative to Nitrogen, for up to 22 common gases, are stored in
the GFT2. In addition, provision is made for a user-defined conversion factor.
Conversion factors may be applied to all units of measure (except %FS unit) via
LCD/Keypad or serial communication interface.

The following three parameters are available for this function:
K-Factor Mode: Disable, Internal Index, User-Defined (default Disabled)
Internal K Factor Index: 1 – 22 (from internal K-Factor table)
User-Defined K-Factor: 0.001 – 999.9 (default value is 1.000)

NOTE: The conversion factors will not be applied for % FS engineering unit.

Submenu “Alarm Settings”
GFT2 provides the user with a flexible alarm/warning system that monitors the Fluid
Flow for conditions that fall outside configurable limits, as well as visual feedback
for the user via the LCD or via an optically-isolated output. The Flow Alarm has
several attributes which may be configured by the user via LCD/Keypad or serial
communication interface. These attributes control the conditions which cause the
alarm to occur and to specify actions to be taken when the flow rate is outside the
specified conditions.

Depending on the GFT2 function configuration (flow meter or controller) there are
two Alarm algorithms. If GFT2 is configured as flow meter, flow Alarm conditions
become true when the current flow reading is equal to or higher/lower than
corresponding values of high and low flow Alarm levels. If GFT2 is configured as
flow controller, flow Alarm conditions become true when difference between Set
Point value and current flow reading is equal or higher/lower than corresponding
values of High and Low Flow Alarm levels.

Alarm actions can be assigned with preset Delay Interval (0-3600 seconds) to
activate the optically-isolated output (separate for High and Low alarm). Latch
Mode control feature allows each optical output to be latched on or follow the
corresponding alarm status.

The following settings are available for Flow Alarm (see Figure 10):

a) Flow Alarm Mode (Tabular entry)
This function determines whether Flow Alarm is Enabled or Disabled. The following
sections are available: Enabled or Disabled. The default entry is Disabled. Alarm
Mode selections can be set with the UP and DN buttons and are accepted by
pressing ENT button.

b) Low Flow Alarm (Numerical entry)
The limit of required Low Flow Alarm value can be entered in increments of 0.1%
from 0 – 100% FS.
If a Low Alarm occurs and one of the two optional outputs is assigned to the Low
Flow Alarm Event, the optically-isolated output will be activated:
1) For Flow Meter Function: when the flow is less than the Low Flow Alarm value.
2) For flow controller function: when the absolute difference between Set Point
value and actual flow reading is equal or more than the Low Flow Alarm value and
Actual Flow value is less than Set Point value.

The Low Flow Alarm condition is also indicated on the corresponding Process
Information Screen displaying L character.

NOTE: For Flow Meter function, the value of the Low Flow Alarm must be less than
the value of the High Flow Alarm

c) High Flow Alarm (Numerical entry)
The limit of required High Flow Alarm value can be entered in increments of 0.1%
from 0 – 100% FS. If a High Alarm occurs and one of the two optical outputs is
assigned to the High Flow Alarm Event, the optically-isolated output will be
activated for:
a) Flow Meter function: when the flow is more than the High Flow Alarm value.
b) Flow Controller function: when absolute difference between Set Point value and
Actual Flow reading is equal or more than the High Flow Alarm value and actual
flow value is more than Set Point value.

The High Flow Alarm condition is also indicated on the corresponding Process
Information Screen by displaying H character.

NOTE: For Flow Meter function, the value of the High Flow Alarm must be more
than the value of the Low Flow Alarm.

Number

1
2
3
4
5
6
7
8
9

10

11

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47

Table 4: Supported Engineering Units List

Flow Rate

Engineering

Units

%FS

ml/sec
ml/min

ml/hr

ml/day
litr/sec
litr/min

litr/hr

litr/day

m^3/sec
m^3/min

m^3/hr

m^3/day

f^3/sec
f^3/min

f^3/hr

f^3/day
gal/sec
gal/min

gal/hr

gal/day

gram/sec
gram/min

gram/hr

gram/day

kg/sec
kg/min

kg/hr

kg/day

lb/sec
lb/min

lb/hr

lb/day

Mton/min

Mton/hr
lgal/sec
lgal/min

lgal/hr

lgal/day

MilL/min

MilL/hr

MilL/day

bbl/sec
bbl/min

bbl/hr

bbl/day

User

Totalizer

Engineering

Units

%s

ml
ml
ml
ml
litr
litr
litr
litr

m^3
m^3
m^3
m^3

f^3
f^3
f^3
f^3
gal
gal
gal
gal

gram
gram
gram
gram

kg
kg
kg
kg

lb
lb
lb
lb

Mton
Mton

lgal
lgal
lgal
lgal

MilL
MilL
MilL

bbl
bbl
bbl
bbl

User

Description

Percent of full scale

Mililiter per second

Mililiter per minute

Mililiter per hour

Mililiter per day

Liter per second

Liter per minute

Liter per house

Liter per day

Cubic meter per second

Cubic meter per minute

Cubic meter per hour

Cubic meter per day

Cubic feet per second

Cubic feet per minute

Cubic feet per hour

Cubic feet per day

Gal per second

Gal per minute

Gal per hour

Gal per day

Grams per second

Grams per minute

Grams per hour

Grams per day

Kilograms per second

Kilograms per minute

Kilograms per hour

Kilograms per day

Pounds per second

Pounds per minute

Pounds per hour

Pounds per day

Metric Ton per minute

Metric Ton per hour

Imperial Gal per second

Imperial Gal per min

Imperial Gal per hour

Imperial Gal per day

Million Litr per minute

Million Litr per hour

Million Litr per day

Barrel per second

Barrel per minute

Barrel per hour

Barrel per day

User Defined