Single-phase 3-wire (1Φ3W)

Model

Name

CH1

CH2

CH3

KEW LOG Soft2

Fixed parameters

KEW 5010

A1

A2

---

Voltage value, Power factor

KEW 5020

A1

A2

---

Voltage value, Power factor

V

A1

A2

Power factor

Three-phase 3-wire (3Φ3W)

General formula is: P=V×(A1×cos(30°-Φ1)+A2×cos(30°+Φ2)),
however, here Φ1=Φ2 is applied.
Therefore: P = √3/2×V×(A1+ A2)×PF

Model

Name

CH1

CH2

CH3

KEW LOG Soft2

Fixed parameters

KEW 5010

A1

A2

---

Voltage value, Power factor

KEW 5020

A1

A2

---

Voltage value, Power factor

V

A1

A2

Power factor

L1
N
L2

A1

V

A2

SOURCE

LOAD

SURCE

LOAD

L1
L2
L3

A1

V

A2