ALTOSONIC V

ModBus Manual 0300 rev07 E

7.30855.35.00

Page 63 of 64

ACCESS MODE 7

=#0

//0, 1: 0=NORMAL, 1=REVERSED DATATYPE

06.08 DATAFIELD 8

=#4000

//RW strings, length=8

ACCESS MODE 8

=#0

//0, 1: 0=NORMAL, 1=REVERSED DATATYPE

06.09 DATAFIELD 9

=#14000

//RW strings, length=16

ACCESS MODE 9

=#0

//0, 1: 0=NORMAL, 1=REVERSED DATATYPE

-----------------------------------------------------------------------------------------------------------------------------------------------------------
07 [MODBUS MASTER POLLBLOCK DEFINITION]

07.01 NUMBER_OF_POLLBLOCKS_TO_USE =#1 //1..20 NUMBER OF POLLBLOCKS TO TRANSMIT
07.02 REQUEST_TO_RESPONSE_TIMOUT =#10 //35 ms units

POLLBLOCK:
SLAVEID - MODBUS SLAVE ADDRESS, 0..247

MASTERREGISTER - ADDRESS OF DATA IN ALTOSONIC_V, 0..10000
SLAVEREGISTER - ADDRESS OF DATA IN SLAVE, 0..10000

N_POINTS - NUMB OF DATA ITEMS TO TRANSFER

(NOT REGISTERS BUT DATATYPES) 0..255
FUNCTION - FUNCTION TO USE FOR DATA TRANSFER,1..16

DATATYPE - DATATYPE FOR CODING,DECODING AND VERIFICATION
1=boolean

2=integer

3=longinteger
4=float

5=double

DATANOTATION - NORMAL(0) OR REVERSED NOTATION(1) OF THE DATATYPE
DELAY - DELAY TO TRANSMIT NEXT POLLBLOCK 1..30000


07.03

NR SLAVEID MASTERREG. SLAVEREG. N_POINTS FUNC DATATYPE DATANOT. DELAY

01 #1 #2000 #7501 #2000 #1 #1 #0 #5
02 #1 #3010 #3501 #10 #3 #2 #0 #5

03 #1 #7010 #7501 #10 #3 #4 #0 #5

04 #1 #5010 #5501 #10 #3 #3 #0 #5
05 #1 #7018 #7501 #2 #3 #4 #0 #5

06 #0 #0 #0 #1 #1 #1 #0 #1
07 #0 #0 #0 #1 #1 #1 #0 #1

08 #0 #0 #0 #1 #1 #1 #0 #1

09 #0 #0 #0 #1 #1 #1 #0 #1
10 #0 #0 #0 #1 #1 #1 #0 #1

11 #0 #0 #0 #1 #1 #1 #0 #1
12 #0 #0 #0 #1 #1 #1 #0 #1

13 #0 #0 #0 #1 #1 #1 #0 #1

14 #0 #0 #0 #1 #1 #1 #0 #1
15 #0 #0 #0 #1 #1 #1 #0 #1

16 #0 #0 #0 #1 #1 #1 #0 #1

17 #0 #0 #0 #1 #1 #1 #0 #1
18 #0 #0 #0 #1 #1 #1 #0 #1

19 #0 #0 #0 #1 #1 #1 #0 #1
20 #0 #0 #0 #1 #1 #1 #0 #1