Profibus settings, 3 menu c, setup – KROHNE MFC 400 Profibus User Manual
Page 47
PROFIBUS SETTINGS
5
47
MFC 400
www.krohne.com
06/2013 - 4002835301 - AD MFC 400 PROFIBUS R01 en
5.3 Menu C, Setup
if condensed status and diagnosis
condensed status and diagnosis
condensed status and diagnosis
condensed status and diagnosis handling selected:
No.
Function
Settings / descriptions
C1Process Input
C1.5
Diagnostics
-
It is strongly recommended to use the default classification of the variable "Event groups" mentioned below. If the
default classification should be changed please note!
1
C1.5.7
Proc: Signal Low
Select:Out of Specification (default)FailureInformationMaintenance
RequiredFunction Check
1
C1.5.8
Proc: Signal Search
Select:Failure (default)InformationMaintenance RequiredFunction CheckOut
of Specification
1
C1.5.9
Proc: Current Input
Select:Failure (default)InformationMaintenance RequiredFunction CheckOut
of Specification
1
C1.5.10
Proc: 2 Phase Flow
Select:Out of Specification (default)FailureInformationMaintenance
RequiredFunction Check
1
C1.5.11
Proc: System Control
Select:Information (default)Maintenance RequiredFunction CheckOut of
SpecificationFailure
1
C1.5.12
Config: Totaliser
Select:Out of Specification (default)FailureInformationMaintenance
RequiredFunction Check
1
C1.5.13
Electr: Power Failure
Select:Information (default)Maintenance RequiredFunction CheckOut of
SpecificationFailure
1
C1.5.14
Electr: IO Connection
Select:Out of Specification (default)FailureInformationMaintenance
RequiredFunction Check
1
1 Below mentioned definitions for both diagnosis and status will be internally used for PROFIBUS diagnosis and status handling of the
classifications stated below which will be possible for the variable "Event groups":
"F"
Failure
diagnosis: DIA_MAINTENANCE_ALARM (Maintenance alarm (40))
status: BAD - maintenance alarm
"S"
Out of specification
diagnosis: DIA_MAINTENANCE_DEMAND (Maintenance demanded (41))
status: UNCERTAIN - process related, no maintenance
"M"
Maintenance required
diagnosis: DIA_MAINTENANCE (Maintenance required (37))
status: GOOD - maintenance demanded
"C"
Function check
diagnosis: DIA_FUNCTION_CHECK (Function check (42))
status: GOOD - function check
"I"
Information
diagnosis: NO DIAGNOSIS EVENTS (no diagnosis events)
1
status: GOOD - ok
1 Bit "EXTENSION_AVAILABLE" of parameter DIAGNOSIS will be set if at least one Bit of parameter "DIAGNOSIS_EXTENSION" has been
set.