Profibus pa, 4 technical data – KROHNE MFC 400 Profibus User Manual

Page 18

background image

3

PROFIBUS PA

18

MFC 400

www.krohne.com

06/2013 - 4002835301 - AD MFC 400 PROFIBUS R01 en

3.4 Technical data

Hardware

Type

PROFIBUS MBP interface according to IEC 61158-2 with

31.25 kbits/s; voltage mode

[MBP = Manchester Coded Bus Powered]

Connection

Independent of polarity at electrical connection

Base current

10.5 mA

FDE

Yes, separate fault disconnection electronics provided (FDE = Fault

Disconnection Electronics)

Fault current

6 mA (fault current = max. continuous current – base current)

Starting current

<12 mA

Ex approval

Ex ia IIC or Ex ib IIC/IIB, FISCO Device

For detailed information refer to standard product documentation.

Software

GSD

GSD file on CD-ROM or from internet site

Supported GSD:

KRO14513.GSD

PA139742.GSD

Device profile

PROFIBUS PA Profile 3.02; conformance class B, compact

Address range

0…126 (default 126)

0…125 via PROFIBUS service set_slave_add

0…126 via local display

126 via factory_reset = 2712

Local control

Local display and operator interface at device

SAPs

2 x MS1 SAPs – acyclic interface to PLC

3 x MS2 SAPs – the number of MS2 Service Access Points is typically

equal to the maximum number of master class 2 tools

Function blocks

1 x TB = Transducer Block: contains the parameters and functions

defined in PA Profile 3.02

1 x PB = Physical Block: contains the parameters defined in PA

Profile 3.02

8 x AI = Analog Input Blocks: contains the parameters defined in PA

Profile 3.02

3 x TOT = Totalizer Function Blocks: contains the parameters defined

in PA Profile 3.02