beautypg.com

Profibus dp – KROHNE MFC 400 Profibus User Manual

Page 12

background image

2

PROFIBUS DP

12

MFC 400

www.krohne.com

06/2013 - 4002835301 - AD MFC 400 PROFIBUS R01 en

INFORMATION!
During network configuration the user has to define which function block outputs of the signal
converter should be transferred cyclically to the master. This is performed by a bus
configuration tool (e.g. "HW- Config" for PC-S7 from Siemens). This tool offers specific functions
as follows:
1. It is possible to configure an "Empty" block (the code of an "Empty" block is defined as 0x00) on

each block number. This implies: no data are transmitted in the cyclic data telegram for this
block.

2. There is NO "Totaliser (TOT)" function block allowed on block position 1, 2, 3, 7, 8, 9, 10 and 11!

On these positions, only an "Analog Input (AI)" function block or an "Empty" block is allowed!
(Note: All codes supported by "Analog Input (AI)" - and "Totaliser (TOT)"

function blocks will

be found in the corresponding GSD files.)

3. There is NO "Analog Input (AI)" function block allowed on block position 4, 5 and 6! On these

positions, only a "Totaliser (TOT)" function block or an "Empty" block is allowed!

4. There is a choice of 7 different totaliser functions, which can be allocated to the blocks 4, 5

and/or 6.