beautypg.com

Commissioning / operation, 2 output data – KROHNE MFC 400 Profibus User Manual

Page 30

background image

4

COMMISSIONING / OPERATION

30

MFC 400

www.krohne.com

06/2013 - 4002835301 - AD MFC 400 PROFIBUS R01 en

4.2.2 Output data

Output data is transferred from the master to the PROFIBUS device to control the totalizers.
Behaviour and coding is described by the following tables.

Module types (defined in GSD):

Coding of SetTot

Coding of ModeTot

Total

cyclic transfer of the totalizer value with status to the master (no output data)

(no output data)

(no output data)

(no output data)

SetTot + Total

cyclic transfer of the totalizer value with status to the master +

cyclic control data from master to the slave via the parameter SetTot

ModeTot + Total

cyclic transfer of the totalizer value with status to the master +

cyclic control data from master to the slave via the parameter ModeTot

SetTot +

ModeTot + Total

cyclic transfer of the totalizer value with status to the master +

cyclic control data from master to the slave via the parameters SetTot and ModeTot

(in this order)

SetTot

cyclic control data from master to the slave via the parameter SetTot

ModeTot

cyclic control data from master to the slave via the parameter ModeTot

SetTot + ModeTot

cyclic control data from master to the slave via the parameters SetTot and ModeTot

(in this order)

SetTot = 0

Totalizer is totalizing

SetTot = 1

Totalizer is reset to 0.0 and remains at this value until SetTot is reset to 0. If the

value of SetTot changes from "1" to "0" the totalizer starts counting from 0.0.

SetTot = 2

Totalizer is set to the value defined by PresetTot. PresetTot can be written via an

acyclic service (totalizer in slot 4: Slot 4, Index 32; totalizer in slot 5: Slot 5, Index 32;

totalizer in slot 6: Slot 6, Index 32). If the value of SetTot changes from "2" to "0" the

totalizer starts counting from the current value defined by PresetTot.

Other values are not accepted for SetTot. Values are ignored; totalizer remains in its last valid setting.

ModeTot = 0

True arithmetic integration of the incoming rate values.

ModeTot = 1

Totalization of positive incoming rate values only.

ModeTot = 2

Totalization of negative incoming rate values only.

ModeTot = 3

Totalizer is stopped, no totalization is done.

ModeTot = 248

All incoming rates will be handled as positive values; i.e. negative input values will

be multiplied with "-1.0".

ModeTot = 249

All incoming rates will be handled as negative values; i.e. positive input values will

be multiplied with "-1.0".

Other values are not accepted for ModeTot. Values are ignored; totalizer remains in its last valid setting.

INFORMATION!
Take care that SetTot and ModeTot are level sensitive parameters; e.g. if SetTot is changed from
"0" to "1" the totalizer is reset and stopped. It will not start counting before SetTot is reset to "0"
via the control system or an engineering tool. It is not reset by the PROFIBUS device.