Profibus dp – KROHNE MFC 400 Profibus User Manual
Page 11
PROFIBUS DP
2
11
MFC 400
www.krohne.com
06/2013 - 4002835301 - AD MFC 400 PROFIBUS R01 en
Manufacturer specific Ident. Number (4512 hex)
This setting provides complete functionality of the PROFIBUS DP device. All function Blocks are
available for cyclic data transfer. Device specific diagnosis information is transferred in addition
to the Profile diagnosis.
Cyclic layout:
• AI: Analog Input Function Block
• FB: Function Block
There are separate settings to select the units for local display and PROFIBUS. Modifications of
the units of the display will have no effect on the data transferred via PROFIBUS.
A master class 2 tool is required to modify the units for PROFIBUS transfer.
Valid GSD Modules:
GSD File required:
GSD file KRO14512.GSD
KRO14512.GSD
KRO14512.GSD
KRO14512.GSD is required in this mode. This GSD file provides complete functionality of
the PROFIBUS DP device. All function blocks are available for cyclic data transfer.
Slot
Description
Function Block types
Default unit
1
Mass Flow
AI-FB
kg/s
2
Density
AI-FB
kg/l
3
Temperature
AI-FB
K
4
Mass Totaliser
Totaliser-FB
kg
5
Volume Totaliser
Totaliser-FB
m
3
6
Mass Totaliser
Totaliser-FB
kg
7
Volume Flow
AI-FB
m
3
/h
8
Concentration 1
AI-FB
%
9
Concentration 2
AI-FB
%
10
Concentration Mass Flow 1
AI-FB
kg/s
11
Concentration Mass Flow 2
AI-FB
kg/s
AI-FB
Empty Module
AI: Out
Totaliser-FB
Empty Module
TOT (Id.F.): Total
TOT (Id.F.): SetTot + Total
TOT (Id.F.): ModeTot + Total
TOT (Id.F.): SetTot+ModeTot+Total
TOT (Id.F.): SetTot
TOT (Id.F.): ModeTot
TOT (Id.F.): SetTot + ModeTot
INFORMATION!
If another GSD file is used in the PROFIBUS master system the cyclic data transfer cannot be
established in this setting.