Profibus dp, 8 summary – KROHNE MFC 400 Profibus User Manual
Page 13
PROFIBUS DP
2
13
MFC 400
www.krohne.com
06/2013 - 4002835301 - AD MFC 400 PROFIBUS R01 en
Profile specific Ident. Number (9742 hex)
Functionality is reduced to the requirements which are mandatory in the PA Profile; e.g. 3 x AI-
FB and 1 x TOT-FB are available for cyclic data transfer only. Device specific diagnosis
information is not available via cyclic PROFIBUS services. Nevertheless this behaviour will
improve interchangeability between devices of different vendors because only functions are
available which are provided by all PROFIBUS PA variable area flowmeters. Exchange is possible
without modifying the configuration of the control system.
Cyclic layout:
Valid GSD Modules:
GSD File required:
GSD file PA039742.GSD
PA039742.GSD
PA039742.GSD
PA039742.GSD is required in this mode. This file is provided by PROFIBUS International.
Take care that "Condensed Status and Diagnosis" is not supported by this file.
2.8 Summary
The following table shows a summary of the supported combinations of the PROFIBUS
device with RS485 Physical Interface and PA Profile 3.02:
Slot
Description
Function Block type
Default unit
1
Mass Flow
AI-FB
kg/s
2
Density
AI-FB
kg/l
3
Temperature
AI-FB
K
4
Mass Totaliser
Totaliser-FB
kg
AI-FB
EMPTY_MODULE
AI
Totaliser-FB
EMPTY_MODULE
TOTAL
SETTOT_TOTAL
SETTOT_MODETOT_TOTAL
INFORMATION!
If another GSD file is used in the PROFIBUS master system the cyclic data transfer cannot be
established in this setting.
Ident. Number Selector
Ident.
Number
GSD File
Status
Automatic adaptation mode
4512
KR014512.GSD
Classic / Condensed
9742
PA039742.GSD
1
Classic
Manufacturer specific Ident.
Number
4512
KR014512.GSD
Classic / Condensed
Profile specific Ident. Number
9742
PA039742.GSD
1
Classic
1 This file is provided by PROFIBUS International (www.profibus.com). Take care that "Condensed Status and Diagnosis"
is not supported by this file.