Commissioning / operation – KROHNE MFC 400 Profibus User Manual
Page 34

4
COMMISSIONING / OPERATION
34
MFC 400
www.krohne.com
06/2013 - 4002835301 - AD MFC 400 PROFIBUS R01 en
74
3
("S-") Config_ Totalizer
(default classification / 9)
Configuration related fault(s) detected concerning totalizer. E.g.
"Overflow" of a totalizer – counting starts with "zero". The
measurement accuracy may be reduced. But still the
measurement value follows the source. Check fault(s) detected /
4 - if the fault(s) cannot be cleared contact the service
department of the manufacturer with an indication of the
problem(s).
75
3
("S-") Proc: Signal Low
(default classification / 9)
Process related fault(s) detected concerning the "sensor". E.g.
not reached accuracy. The measurement accuracy may be
reduced. But still the measurement value follows the source.
Check fault(s) detected / 4 - if the fault(s) cannot be cleared
contact the service department of the manufacturer with an
indication of the problem(s).
76
3
("S-") Proc: 2 Phase Flow
(default classification / 9)
Process related fault(s) detected concerning the "2 Phase Flow".
E.g. an unknown accuracy. The measurement accuracy may be
reduced. But still the measurement value follows the source.
Check fault(s) detected / 4 - if the fault(s) cannot be cleared
contact the service department of the manufacturer with an
indication of the problem(s).
77
3
("F-") Proc: Signal Search
(default classification / 9)
Process related error(s) detected concerning the "sensor". E.g. a
very high damping in the sensor. Related output values are
invalid. A repair or replacement of the device can be necessary.
Check error(s) detected / 4 - restart the device – if the error still
occur contact the service department of the manufacturer.
78
3
("S-") Electr: IO Connection
(default classification / 9)
Converter related fault(s) detected concerning interconnection of
modules and terminals. E.g. an open or short circuit at the related
terminal. The measurement accuracy may be reduced. But still
the measurement value follows the source. Check fault(s)
detected / 4 - if the fault(s) cannot be cleared contact the service
department of the manufacturer with an indication of the
problem(s).
79
3
("F-") Proc: Current Input
(default classification / 9)
Process related error(s) detected concerning "current input
modules". Related output values are invalid. A repair or
replacement of the device can be necessary. Check error(s)
detected / 4 - restart the device – if the error still occur contact
the service department of the manufacturer.
81
3
("I-") Electr: Info. Operation
(classification fixed - not changeable)
Converter Electronic related information. Just information. No
impact on measurement expected. Check information just
present / 7.
82
3
("I-") Config: No Meas. Value
(classification fixed - not changeable)
Configuration / measurement value related information. Just
information. No impact on measurement expected. Check
information just present / 7.
97
3
I - Parameter Update in Progress
(classification fixed - not changeable)
GDC warm start in progress / 8
99
3
F - No Meas. Value
(classification fixed - not changeable)
Measurement value not available (or no more available) / 8.
(status bit "F – Electronics" will be set too)
100
3
F - Parameter Update Error
(classification fixed - not changeable)
Error occurred during parameter update of PROFIBUS
parameters / 8.
(status bit "F – Configuration" will be set too)
101
3
F - No Device Communication
(classification fixed - not changeable)
No communication between basic device and PROFIBUS module /
8.
(status bit "F – Electronics" will be set too)
Bit Number
sup
p
orted
De
sc
ription
Remedy