Operation – KROHNE OPTISYS SLM 2100 EN User Manual
Page 49

OPERATION
5
49
OPTISYS SLM 2100
www.krohne.com
03/2014 - 4002737302 - MA OPTISYS SLM 2100 R02 en
C4, extended setup
Level
Designation / function
Settings / descriptions
This submenu allows to set the initial parameters for commissioning of the meter.
C4.1
Maximum depth
Definition of the maximum depth.
C4.2
Start position
Definition of the start position.
C4.3
Blind zone
Definition of the blind zone.
C4.4
Rake height
Definition of the rake height.
C4.5
Cleaning
Settings of the corresponding relay.
C4.5.1
Activation
This function allows to activate cleaning:
Options:
•
off
•
timer interval
•
counter interval
C4.5.2
Counter interval
This menu defines the number of measurement cycles between cleaning
(This menu is displayed only if counter interval is selected in C4.5.1).
C4.5.3
Timer interval
This menu defines the time of the cleaning intervals (This menu is displayed
only if timer interval is selected in C4.5.1);
Range: 10…999 min
C4.5.4
Pump lead time
Definition of pump lead time. (This menu is displayed only if cleaning is
activated in C4.5);
Range: 0…120 s
C4.5.5
Cleaning cycle
In this menu a the number of cleaning cycles can be set;
Range: 0…99
C4.5.6
External pump
This menu defines if the external pump is controlled by the relays K3
(Choose "yes" or "no").