Trouble call limit (dialer runaway prevention)” on – Fire-Lite MS-10UD Series FACP User Manual
Page 89
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
89
Master Programming Level
Programming
Trouble Call Limit (Dialer Runaway Prevention)
The Call Limit option limits the number of DACT trouble calls to the Central Station, to a pro-
grammed amount between 0 and 99, for each unique trouble within a 24 hour period. All call limit
counters reset (clear) at each midnight. Separate limit counters keep track of each unique type of
trouble. Note that the number of phone line (communication) faults called to the Central Station
are not limited by this feature. No subsequent restoral message is sent to the Central Station(s) for
a particular trouble whose call limit has been reached. Local DACT annunciation will still track the
particular trouble and restoral.
To set the Trouble Call Limit, press 3 while viewing Central Station Screen #2. The following
screen will be displayed.
Enter a value between 00 and 99, then press Enter to set the Call Limit to this value.
Service Terminal
The FACP can be programmed remotely from a PC using a modem and telephone line. Informa-
tion can also be retrieved from the FACP using the same method. The Upload/Download option
allows an operator to set the necessary parameters to allow the uploading and downloading of data
between the FACP and PC. The Service Terminal selection provides the means for entering these
parameters.
Pressing 1 while viewing Onboard DACT Screen #2 will cause the following screens to appear:
Ring Count
The ring count designates the number of rings allowed on the phone line prior to answering an
incoming call from a service terminal. The factory default is 0 which means the control panel will
not answer an incoming call. This entry may be programmed for 1 to 25 rings.
Secondary # System Off Normal
LB
LX
Secondary # System Test Message
RP
000
Secondary # System Abnormal Test Message
RP99
000
Secondary # Power Supply Sync Fault
OU
OV
Secondary # Upload/Download Request
RB
000
Secondary # Upload Successful
RS
000
Secondary # Download Successful
RS
000
Secondary # Upload/Download Failed
RU
000
Secondary # Voice EVAC Fault
ET
ER
Secondary # Power Supply Sync Fault
OU
OV
Table 3.7 SIA-DCS Secondary # Event Codes (Continued)
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=CALL LIMIT
Central Station Screen #2
TROUBLE CALL LIMIT
RANGE 00-99 TROUBLES
Backup Reporting Screen
NOTE: Entering a value of 00 will disable the Trouble Call Limit allowing the DACT to call the
Central Station an unlimited amount of times. This is the factory default setting.
DACT
1=SERVICE TERMINAL
2=SUPERV PHONE LINE
Onboard DACT Screen #2
SERVICE TERMINAL
1=RING COUNT 0
Service Terminal Screen
SERVICE TERMINAL
1=RING COUNT
Service Terminal Screen #2