Table 3.3 – Fire-Lite MS-10UD Series FACP User Manual
Page 83
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
83
Master Programming Level
Programming
The following tables list all of the Events and their default Event Codes for the Ademco Contact ID
and SIA-DCS Communication Formats.
Zone Alarm Type
Ademco Contact ID
SIA-DCS Format
Active
Active
Restoral
Pull-Station
115
FAx
FHx
Waterflow
113
SAx
SHx
Waterflow Nonsilenceable
113
SAx
SHx
Combo
113
SAx
SHx
Combo AutoResettable Supervisory
113
SAx
SHx
2-Wire Detector
111
FAx
FHx
Normally Open Contact
110
UAx
UHx
Fire
110
FAx
FHx
Tamper
144
TAx
THx
Supervisory
200
FSx
FVx
Supervisory AutoResettable
200
FSx
FVx
Medic-Alert 100
MAx
MHx
Hazard-Alert
150
PAx
PHx
Tornado-Alert
150
PAx
PHx
Proc-Mon
200
IAx
IRx
Procmon-AR
200
IAx
IRx
AC-Loss-Mon
301
ATx
ARx
Drill-Switch
604
FIx
FKx
Drill-Switch AutoResettable
604
FIx
FKx
Table 3.3 Zone Alarm Type Event Codes
NOTE: A detector freeze condition will be reported as a Supervisory Event Code.