Ann-audio options screen, Ann-sec enable, Onboard dact – Fire-Lite MS-10UD Series FACP User Manual
Page 79
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
79
Master Programming Level
Programming
ANN-AUDIO Options Screen
Pressing 1 for ANN-AUDIO Options while viewing ANN-BUS Screen #3 will cause the following
screen to be displayed:
This screen shows the Input Zone that has been assigned to be the All-Call Zone. In this example,
Zone 1 is the All-Call Zone. The All-Call Zone can be changed by pressing the 1 key while view-
ing the ANN-AUDIO Options Screen. The following screens will be displayed.
These screens allow the programmer to select which Input Zone will be assigned as the All-Call
Zone.
ANN-SEC Enable
The ANN-SEC option must be enabled if any modules are connected to the ANN-SEC option card
at J13. To enable the Secondary ANN-BUS, press 2 while viewing ANN-BUS Screen #3 so that the
display reads ANN-SEC ENABLE YES. Each press of the 2 key will cause the display to toggle
between ANN-SEC ENABLE YES and ANN-SEC ENABLE NO. The factory default setting is ANN-
SEC ENABLE NO.
Onboard DACT
The Onboard DACT (Digital Alarm Communicator/Transmitter) provides communication to a cen-
tral station. Pressing 2 while viewing the Option Module Screen will cause the following screens
to be displayed:
Primary Phone
Press 1 while viewing Onboard DACT Screen to program the type of primary phone line being
connected to the DACT. The following screen will be displayed:
Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break ratio of 67/33, or 3
to select Rotary dialing with a make/break ratio of 60/40.
PROGRAMMING
1=ANN-AUDIO OPTIONS
ANN-BUS Screen #3
ANN-AUDIO OPTIONS
1=ALL CALL ZONE 1
ANN-AUDIO Options Screen
ANN-AUDIO ALL CALL
1=NO ALL CALL ZONE
2=INPUT ZONE 1
3=INPUT ZONE 2
All-Call Options Screen #1
ANN-AUDIO ALL CALL
1=INPUT ZONE 3
2=INPUT ZONE 4
3=INPUT ZONE 5
All-Call Options Screen #2
ANN-AUDIO ALL CALL
1=INPUT ZONE 9
2=INPUT ZONE 10
All-Call Options Screen #4
(MS-10UD Only)
ANN-AUDIO ALL CALL
1=INPUT ZONE 6
2=INPUT ZONE 7
3=INPUT ZONE 8
All-Call Options Screen #3
(MS-10UD Only)
OPTION MODULES
1=ANN-BUS
2=ON BOARD DACT
Option Module Screen
ANN-BUS
1=ANN-AUDIO OPTIONS
2=ANN-SEC ENABLE NO
ANN-BUS Screen #3
ON BOARD DACT
1=PRIM PHONE TCH TNE
2=SCND PHONE TCH TNE
3=CENTRAL STATION
ON BOARD DACT
1=SERVICE TERMINAL
2=SUPERV PHONE LINE
Onboard DACT Screen 1
Onboard DACT Screen 2
PHONE LINE
1=TOUCHTONE
2=ROTARY 67/33 (EURO)
3=ROTARY 60/40 (U.S.)
Primary Phone Type Screen