Fire-Lite MS-10UD Series FACP User Manual
Page 62
62
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Programming
Master Programming Level
The following examples show the editing of Input Zone 1:
Enable/Disable Zone
To Enable or Disable the zone, press the 1 key while viewing the Edit Input Zone Screen #2. Each
press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No is
selected, the zone will be disabled by the control panel, preventing the circuit from reporting alarms
and troubles to the panel. The control panel LCD will display the zone which has been disabled
and FACP will turn on the Trouble LED.
Type
To select the type of zone being programmed, press the 2 key while viewing the Edit Input Zone
Screen #2. This will cause the control panel to display the following Zone Type Screen:
Pressing the down arrow key will display additional zone types as indicated in the following table.
Some of the following Zone Types are not available for Canadian applications. Refer to “Canadian
Option” on page 74 for additional details.
Zone Type
Action When Activated
Pull-Station
Fire Alarm
Waterflow
Fire Alarm Delayed (uses waterflow delay)
Waterflow Nonsilenceable
Fire Alarm (uses waterflow delay)
Combo
Fire/Supervisory (uses waterflow delay)
Combo AutoResettable
Fire/Supervisory AR, nonlatching (uses waterflow delay)
2-Wire Detector
Fire Alarm
Normally Open Contact
Fire Alarm
Fire
Fire Alarm
Tamper
Supervisory
Supervisory
Supervisory, latching
Supervisory AutoResettable
Supervisory, nonlatching
Medic-Alert Supervisory,
latching
Hazard-Alert
Supervisory, latching
Tornado-Alert
Supervisory, latching
Table 3.1 Zone Types
INPUT ZONE 1
1=ENABLED YES
2=TYPE PULL STATION
3=VERIFICATION NO
Edit Input Zone Screen #2
INPUT ZONE 1
1=PAS/PRE-SIG DELAY
NO DELAY
Edit Input Zone Screen #3
Edit Input Zone Screen #5
INPUT ZONE 1
1=ADJECTIVE/NOUN
2=DESCRIPTION
INPUT ZONE 1
1=FREEZE SUPV. NO
2=ACC MSG# 2
Edit Input Zone Screen #4
INPUT ZONE
1=ENABLED
2=TYPE
3=VERIFICATION
Edit Input Zone Screen #2
ZONE TYPE
1=PULL STATION
2=WATERFLOW
3=WATERFLOW NS
Zone Type Screen #1