Fire-Lite MS-10UD Series FACP User Manual
Page 82
82
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Programming
Master Programming Level
Enter the digits as you would like the number to be dialed. For example, if it’s necessary to dial 9
before dialing a number outside the building, you may wish to pause after dialing 9. Enter 9 fol-
lowed by D for a three second pause, or E for a five second pause then the phone number followed
by an F to indicate the end of the number.
Communication Format
Pressing 1 while viewing Primary/Secondary Screen #3 will cause the following screen to be dis-
played:
The Communication Format is determined by the type of receiver that the DACT is transmitting to.
Consult your Central Station for proper selection or consult our factory representatives. For any
format chosen, the control panel automatically programs all of the event codes.
Select the Communication Format by pressing the corresponding number key while viewing the
Comm Format screen. The following table describes each format:
Event Codes
Pressing 2 while viewing Primary/Secondary Screen #3 will cause the following screen to be dis-
played:
Pressing the down arrow key allows viewing of all Events associated with the selected Communi-
cation Format. Pressing the number corresponding to the event displayed in each screen will dis-
play its default active and restoral event codes which can be customized by the programmer.
For example, if Ademco Contact ID is the selected format, pressing 3 for Zone 3 Alarm will display
the following screen which allows the Event Code to be changed from the default value.
The following table lists the Zone Alarm Types that can be programmed for zones 1 through 10 and
the corresponding Event Codes for Ademco Contact ID and SIA DCS Formats. Note that Table 3.4
on page 84, Table 3.5 on page 85, Table 3.6 on page 86 and Table 3.7 on page 87 list the default set-
tings for Zone 1 through Zone 10. These can be changed to any of the Types listed in Table 3.3.
Screen Selection
Communication Format Description
ADEMCO CONTACT ID
Contact ID, DTMF, 1400/2300 ACK
SIA-DCS-8
Security Industry Association, 8 messages per call
SIA-DCS-20
Security Industry Association, 20 messages per call
Table 3.2 Communication Formats
CENTRAL STATION
1=COMM FORMAT
2=EVENT CODES
Primary/Secondary Screen #3
COMM FORMAT
1=ADEMCO CONTACT ID
2=SIA-DCS-8
3=SIA-DCS-20
EVENT CODES
1=ZONE 1 ALARM
2=ZONE 2 ALARM
3=ZONE 3 ALARM
Event Code Screen
ZONE 3 ACTIVE
115
NOTE: The third character in the SIA-DCS Format (x in the table below) represents the zone
number.