Operating Instructions
Process Monitor Operation
•
Communicate the supervisory condition to the Central Station
•
The supervisory relay is activated
•
The alarm relay is not activated
•
Silenced alarms are not resounded
•
Timers are not started
•
Store event in history buffer
•
Terminate upload or download communications
A typical Supervisory event would be displayed as illustrated in the following:
In the preceding example:
• FROZEN SUPRV - indicates zone detector is below approximately 45
o
F
Note that, like alarms, supervisory signals latch, except when programmed for supervisory autore-
settable. Supervisory activations do not cause silenced alarms to resound, as do other alarm condi-
tions. Open circuits in supervisory wiring are processed by the control panel the same way as other
trouble conditions. Refer to “Alarm Operation” on page 99, for a description of the information
displayed on the control panel LCD.
4.7 Process Monitor Operation
Process Monitor operation will initiate the following events:
•
The piezo sounder pulses ¼ second On and ¼ second Off
•
The LCD displays a process monitor message along with the device name, type,
adjective/noun, associated zones and time/date
•
Communicate the process monitor condition to the Central Station (if the default event code
has been changed from 000 to a reportable event code)
•
Relays programmed for process monitoring will be activated
•
The alarm relay is not activated
•
Silenced alarms are not resounded
•
Timers are not started
•
Store event in history buffer
•
Activate appropriate LED on the ANN-LED annunciator (required for this application)
Note that, like supervisories, process monitor signals latch, except when programmed for process
monitor autoresettable.
4.8 Hazard/Tornado Condition Operation
Hazard/Tornado operation is intended for Manual activation.
Hazard/Tornado Condition operation will initiate the following events:
•
The piezo sounder pulses ¼ second On, ¼ second Off
•
The LCD displays a hazard message along with the device name, type, adjective/noun,
associated zones and time/date
•
Communicate the hazard condition to the Central Station (if the default event code has been
changed from 000 to a reportable event code)
•
Relays programmed for hazard will be activated
FREEZE SUPERVISORY
ZONE 05 FROZEN SUPRV
10:00A 100913