Fire-Lite MS-10UD Series FACP User Manual
Page 63
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
63
Master Programming Level
Programming
While viewing any Zone Type screen, select the type of zone being programmed by pressing the
corresponding keyboard number key. The display will return to Edit Input Zone Screen #2 and
indicate the selection next to the Type option.
Verification
Alarm verification is used to confirm that a smoke detector activation is a true alarm condition and
not a false alarm. This feature is selected by pressing 3 while viewing the Edit Zone Screen #2 so
that the display reads Verification On. Each time the 3 key is pressed, the display will toggle
between Verification On and Verification Off. For a detailed description, refer to “Alarm Verifica-
tion (None or One Minute)” on page 104.
Note that verification can only be enabled for a zone that is programmed as a smoke detector type.
Zones programmed for any other type will not allow the Verification feature to be enabled. Do not
use the verification feature if a mix of smoke detectors and normally open contact devices are con-
nected to the same zone.
PAS/Pre-Signal Delay
Pressing 1 while viewing Edit Input Zone Screen #3 will display the following screen:
Pre-signal
The Pre-signal option programs the zone to delay panel activation for a preprogrammed time delay
of up to three minutes while allowing for visual verification by a person. Note that the alarm relay
and communicator will respond to the initial alarm immediately. To enable the Pre-signal feature,
press 2 while viewing PAS/Pre-Signal Screen. Refer to “Presignal” on page 102.
PAS
The PAS (Positive Alarm Sequence) option will program the zone to delay panel activation (includ-
ing alarm relay and communicator) for a period of 15 seconds plus a programmable time of up to 3
minutes. To enable the PAS feature, press 3 while viewing the PAS/Pre-Signal Screen. This option
is available only for circuits programmed as smoke detector circuits. Refer to “Positive Alarm
Proc-Mon
Piezo
Procmon-AR
Piezo, nonlatching
AC-Loss-Mon
Trouble
Ack-Switch
Acts like panel Acknowledge Key
Sil-Switch
Acts like panel Alarm Silence Key
Drill-Switch
Acts like panel Drill Key
Reset-Switch
Acts like panel Reset Key
PAS-Bypass
Positive Alarm Sequence Disable
Drill-Switch AutoResettable
Acts like panel Drill Key, nonlatching
Table 3.1 Zone Types
NOTE:
Almost any Input Zone type can activate an ACC-25/50ZST audio zone and output an
assigned message with the exception of ACKNOWLEDGE, SILENCE, RESET and PAS
BYPASS Switches. The DRILL Switch (or input programmed as a drill switch) will cause all of
the corresponding ACC-25/50ZST audio zones to go active and will output Message 1.
INPUT ZONE
1=ENABLED
2=TYPE
3=VERIFICATION
Edit Input Zone Screen #2
INPUT ZONE #
1=PAS/PRE-SIG DELAY
NO DELAY
Edit Input Zone Screen #3
PAS/PRE-SIG DELAY
1=NO DELAY
2=PRE-SIGNAL DELAY
3=PAS DELAY
PAS/Pre-Signal Delay Screen