Controls and Indicators
1.3 Controls and Indicators
LCD Display
The FACP uses an 80-character (4 lines X 20 characters)
high viewing angle LCD display. The display includes a
long life LED backlight that remains illuminated. If AC
power is lost and the system is not in alarm, the LED back-
light will turn off to conserve batteries.
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and LED
indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25
keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
Function keys:
•
Acknowledge/Step
•
Alarm Silence
•
Drill
•
System Reset (lamp test)
Service/program keys:
•
Keys labeled 1 to 9
•
* key
•
# key
•
0 (recall) key
•
1st Event key
•
Clear key
•
Escape key
•
Mode key
•
Four cursor keys (up, down, left and right)
•
Enter key
LED Indicators
LEDs are provided to annunciate the following conditions:
•
Fire Alarm - red LED
•
Supervisory - yellow LED
•
AC Power - green LED
•
System Trouble - yellow LED
•
Alarm Silence - yellow LED
•
Primary Phone Line Active (on circuit board) - red LED
•
Secondary Phone Line Active (on circuit board) - red LED
•
Kiss-off (on circuit board) - green LED
Local Piezo Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance, process
monitor and supervisory conditions as follows:
•
Alarm - on steady
•
Trouble - pulse 1 second on and 1 second off
•
Maintenance - pulse 1 second on and 1 second off
•
Supervisory - pulse ½ second on and ½ second off
•
Process Monitor - pulse ¼ second on and ¼ second off
SYSTEM ALL NORMAL
10:00A 012105
Figure 1.3 Membrane/Display Panel