Medical Alert Condition Operation
Operating Instructions
•
The alarm relay is not activated
•
Silenced alarms are not resounded
•
Timers are not started
•
Store event in history buffer
•
Activate appropriate LED on the ANN-LED annunciator (required for this application)
Hazard conditions latch.
4.9 Medical Alert Condition Operation
Medical alert operation is:
•
not intended for nurse call stations (applications) per UL1069.
•
not intended for signaling professional medical staff.
•
to be used for summoning security guards or other trained personnel within the facility
•
intended for Manual activation.
Medical Alert Condition operation will initiate the following events:
•
The piezo sounder ¼ second On, ¼ second Off
•
The LCD displays a medical alert message along with the device name, type, adjective/noun,
associated zones and time/date
•
Communicate the medical alert condition to the Central Station (if the default event code has
been changed from 000 to a reportable event code)
•
Relays programmed for medical alert will be activated
•
The alarm relay is not activated
•
Silenced alarms are not resounded
•
Timers are not started
•
Store event in history buffer
•
Activate appropriate LED on the ANN-LED annunciator (required for this application)
Medical alert conditions latch.
4.10 Disable/Enable Operation
Input zones which are disabled do not cause an alarm or any zone activation. Disabled NACs are
held in the off state. All disabled zones/NACs are treated as if they were in trouble, with the excep-
tion being the status label that will be displayed is DISABL.
4.11 Waterflow Circuits Operation
If an alarm exists from a zone that is a waterflow non-silenceable type, the Alarm Silence key will
not function.