Fire-Lite MS-10UD Series FACP User Manual
Page 126
126
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
NFPA Standard-Specific Requirements
The following figure illustrates an example of Central Station/Remote Station Reporting using a
411UD. The relay contacts from the MS-5UD/MS-10UD may be used to trip any dialer UL listed
for Central Station/Remote Station Reporting Services.
Figure B.1 MS-5UD/MS-10UD FACP Connection to 411UD
Channel1
Channel 2
Channel 3
Channel 4 (2.2K ELR)
Relay Output (DACT Trouble) from 411UD
FACP Supervisory Relay
FACP Alarm Relay
FACP Trouble Relay
J4 Not Installed
411UD
1
2
3
4
5
6
7
8
+ 24 VDC nonresettable power
- 24 VDC nonresettable power
2.2K ELRs P/N 27070
1
2
3
4
5
6
7
8
9
1 2 3 4 5 6 7
FACP
Jumper -VDC to Trouble Relay contact
Trouble Input
(non-supervised,
power-limited)
411UD
FACP
Alarm
TB2-1
TB8-1
TB2-2
TB8-3
Trouble
TB2-3
TB8-4
TB2-4
TB8-6
Supervisory
TB2-5
TB8-7
TB2-6
TB8-9
Table B.1 411UD Connections to FACP