Fire-Lite MS-10UD Series FACP User Manual
Page 84
84
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Programming
Master Programming Level
Ademco Contact ID Format - Primary Central Station Phone Number
The information shown in Table 3.4 is automatically programmed for the Primary Central Station
phone number Event Codes when Ademco Contact ID Format is selected. To disable event report-
ing, select the desired Event Code to be disabled and press 0 or Clear and then Enter to disable it.
(Enter must be pressed to save the selection. Pressing Escape will not save the selection).
Event Description
Event Code Settings
Zone Code
Active
Primary # Zone 1 - 10 Alarm
115
001 - 010
Primary # Zone 1 - 10 Disabled
570
001 - 010
Primary # Drill
604
000
Primary # AC Fault
301
000
Primary # Zone 1 - 10 Fault
380
001 - 010
Primary # Zone 1 - 10 Dirty
380
001 - 010
Primary # Earth Fault
310
000
Primary # Low Battery Fault
302
000
Primary # No Battery Fault
311
000
Primary # Telco Primary Line Fault
351
001
Primary # Telco Secondary Line Fault
352
002
Primary # NAC #1 Fault
321
001
Primary # NAC #2 Fault
322
002
Primary # NAC #3 Fault
326
003
Primary # NAC #4 Fault
327
004
Primary # NAC #1 Disable
521
001
Primary # NAC #2 Disable
522
002
Primary # NAC #3 Disable
526
003
Primary # NAC #4 Disable
527
004
Primary # Charger Fault
300
000
Primary # Comm Trouble Primary #
354
001
Primary # Comm Trouble Secondary #
354
002
Primary # Printer Fault
336
000
Primary # ANN-Bus Fault
330
000
Primary # Option Card Fault
333
000
Primary # CS CALC Fault
304
000
Primary # System Off Normal
308
000
Primary # System Test Message
602
000
Primary # System Abnormal Test Message
608
000
Primary # Upload/Download Request
411
000
Primary # Upload Successful
416
000
Primary # Download Successful
412
000
Primary # Upload/Download Failed
413
000
Primary # Voice EVAC Fault
330
000
Primary # Power Supply Sync Fault
300
000
Table 3.4 Ademco Contact ID Primary # Event Codes