Fire-Lite IPDACT Installation Manual User Manual
Page 47

IPDACT Module - Configuration
IV-44
Doc.Dm373-I
Rev. 2.0
completed, an OK will appear on the console. If however there has been as 
error, this could be either: 
q
 “VA unreachable”: It has not been possible to send the register 
command over the IP network. 
q
“No answer”: The register command has been sent but a response 
has not been received from the VisorALARM. 
q
“Error on answer”: The answer from the VisorALARM for the register 
command is wrong. 
 
The automatic device register consist on the attempts of the IPDACT to 
register in the VisorALARM without the operation from the console. When the 
option k) is chosen form the Quick Menu the IPDACT triggers a process in 
which the IPDACT attempts to register until a response from the VisorALARM 
is received. 
During the automatic register none message is dumped in the console. The 
way to know the status of the automatic register is by checking the LED_A. 
This LED is blinking while the IPDACT does not received the response from 
the VisorALARM and will turn off when the register took place. 
The following figure displays the default values. Press z to return to the 
previous menu. 
 -- Quick Install -- 
 a) DHCP client: ON 
 b) IP addr: 192.168.0.100 mask: 255.255.255.0 
 c) Gateway IP: 192.168.0.200 
 d) Account Number: 0 
 e) Supervisory Main: 
 f) Supervisory Backup: 
 g) Maintenance: 
 h) Port: 80 
 i) Register MIP 
 j) Reset 
 k) AutoRegister MIP 
 
 z) Exit 
 
 option: 
IV - 4.6. Monitoring
The rest of the options permit you to inspect the distinct IPDACT aspects and 
to monitor the state and view the enabled events. In order to exit each option, 
press any key which will return you to the main menu. 
Option d) displays the IPDACT general parameters, such as the serial 
number, firmware release, etc. 