beautypg.com

Ii - 2. leds – Fire-Lite IPDACT Installation Manual User Manual

Page 13

background image

IPDACT Module - Description

II-10

Doc.Dm373-I

Rev. 2.0

II - 2. LEDs

The IPDACT has three groups of LEDs that provide information on the status
of each type. These are displayed in the following figures:

Figure 7. LEDs and pins for a IPDACT

The LED labeled “ON” (LD1 for all the versions and releases) is green and
indicates that the IPDACT is powered.

Line status LED: Next to the relays there is a LED labeled LD6. In green this
indicates that the telephone relays are active i.e. the IPDACT intercepts the
telephone line. In normal working mode, this only occurs when the IPDACT
has connectivity with the configured VisorALARM. The relays also activate
when the telephone console activates (please see section IV.2 for further
information). When the control panel is executing maintenance tasks due to a
bi-directional call, the relays are inactive.

LEDs LD2, LD3, LD4 and LD 5 each have an independent connotation:

LED A LD2: Supervision information.

ON: a management frame is sent to the VisorALARM (contact or keep-alive).

OFF: a response is received to the sent management frame. If there is no response,

this remains active, indicating the lack of connectivity with the VisorALARM.

LED B LD3: TO-AP terminal status

ON: the alarms panel telephone line is off hook.

OFF: the alarms panel telephone line is on hook.